:LUH5HTXLUHPHQWV
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations.  The total 
resistance of any branch cannot exceed 40 ohms.  The total wire length of all branches 
cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the Unimode 9600 main circuits must be 
carefully considered to ensure proper operation.  It is important to use the correct type of 
wire, wire gauge and wire run length for each Unimode 9600 circuit.  Reference the chart 
below to specify wire requirements and limitations for each Unimode 9600 circuit.
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk 
of encountering problems can be greatly reduced by exclusively employing electronic 
sounders (such as MA/SS-24D) instead of more electronically noisy notification 
appliances such as electromechanical bells or horns.
7DEOH&8QLPRGH:LUH6SHFLILFDWLRQV
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Circuit Type
Circuit Function
Wire Type and Limitations
Recommended 
Max. Distance
Feet (meters)
Wire Gauge and Compatible Brands
SLC loop
(power-limited)
Connects to 
Addressable 
Devices
Twisted, shielded pair, 40 
ohms maximum per length 
of Style 6 and 7 loops.  40 
ohms per branch maximum 
for Style 4 loops
1
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)
12 AWG (3.25 mm

): Genesis 4410, 
     Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm

):Genesis 4408 & 4608 
      Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm

): Genesis 4406 & 4606
      Signal 98630, Belden 9575, WPW991
     Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm

): Genesis 4402 & 4602
      Signal 98300, Belden 9574, WPW975
      Direct Burial Cable Isotec NP714110VNQ-S
Untwisted, unshielded pair
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm

)
ACS/TERM 
(EIA-485)
(power-limited)
Connects to 
annunciator 
modules and 
ADT-UDACT
Twisted, shielded pair with a 
characteristic impedance of 
120 ohms
6,000 (1,800 m)
18 AWG (0.75 mm

)
EIA-232
(power-limited)
connects to 
remote printer 
and PC computer
Twisted, shielded pair
50 (15 m)
18 AWG (0.75 mm

) minimum
MMF-300 and 
MMF-301
(power-limited)
Initiating Device 
Circuit
Maximum loop wire 
resistance is 40 ohms for the 
MMF-300 and 20 ohms for 
the MMF-301
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm

)
MMF-302
(power-limited)
Initiating Device 
Circuit
No more than a 2.4 volt drop 
allowed at end of circuit.  
Maximum loop wire 
resistance is 25 ohms
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm

)
CMF-300
(power-limited)
Notification 
Appliance 
Circuit
In alarm, no more than a 1.2 
volt drop allowed at end of 
circuit
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm

)
24 VDC 
filtered 
resettable
(power-limited)
Connects to 
4-wire smoke 
detectors
No more than 1.2 volt drop 
allowed from supply source 
to end of any branch
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm

)
24 VDC 
nonresettable
(power-limited)
Connects to 
control modules, 
annunciators and 
accessories
No more than 1.2 volt drop 
allowed from supply source 
to end of any branch
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm

)
CHG-120F
Remote 
secondary power 
source
12 AWG (3.25 mm

) in 
conduit
20 (6 m)
12-18 AWG (3.25 - 0.75 mm

)
Table Footnote
1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.