Specifications
Product Description
Unimode 9600   PN 51336:C    11/06/01
15
EIA-485 (ACS) - TB6
ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-)
EIA-485 (TERM) - TB7
Terminal Mode annunciator connector, Terminal 5 (In +), 6 (In -), 7 (Out +), 8 (Out -)
EIA-232 (ACS) - TB7
PC/Printer Connector, Terminal 1 (Transmit), 2 (Receive), 3 (DTR), 4 (Ground)
Auxiliary Trouble Inputs - J16 & J17
Two-pin connectors which can be used to monitor trouble conditions on auxiliary 
equipment.  They can be connected to the trouble bus of a peripheral such as the ADT-
CHG-120 or to the normally-open dry contacts of a trouble relay.
CAUTION! Do not connect power to these connectors since circuit damage may result.
1.3.1  Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit 
and the total current available from the FACP power supply.
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
3 amps max
per circuit
Resettable Power
for 4-Wire 
Smoke Detectors
Nonresettable 
Power # 1
Nonresettable 
Power # 2
NAC # 1
NAC # 2
Standby
6 amps max
per panel
Alarm
7 amps max
per panel
1     
2     
3   
4    
5     
6    
7    
8
1     
2     
3   
4    
5     
6    
TB4
TB3
Figure 1.1 Current Availability
Refer to the battery calculations  section for  additional information.