Справочник Пользователя для ADT Security Services 9600

Скачать
Страница из 148
Product Description
Accessories
22
Unimode 9600   PN 51336:C    11/06/01
BB-55F
The BB-55F battery box may be used to house two 25 AH batteries, two 60 AH batteries 
or one 100 AH battery.  When the ADT-CHG-120 is mounted in the BB-55F, two 25 AH 
or one 60 AH battery may also be housed in the battery box. 
1.8.4  ADT-CHG-120 Battery Charger
The ADT-CHG-120 is capable of charging up to 120 AH lead-acid batteries with the 
Unimode 9600 FACP.  The FACP battery charger must be disabled when using the 
ADT-CHG-120.  The batteries and charger can be housed in the BB-55F battery box 
which can be mounted up to 20 feet away from the control panel.  Note that when using 
the BB-55F for housing the charger and batteries greater than 25AH, multiple BB-55Fs 
are required.  Refer to the ADT-CHG-120 Manual for additional information.
1.8.5  Annunciators
ADT-ACS Series LED Zone Type Annunciators
The ADT-ACS Series Annunciators remotely display alarm and trouble status as well as 
system status.  In addition, they can provide remote Acknowledge, Silence, Reset and 
Drill functions.  For more detailed information, refer to the appropriate ADT-ACS 
annunciator manual.  Following is a list of annunciators which can be used with the 
Unimode 9600.
• ADT-ACM-16AT Annunciator Control Module annunciates 16 zones with 16 red 
alarm LEDs and 16 yellow trouble LEDs.  In addition, it has a System Trouble 
LED, an On Line/Power LED and a local piezo sounder.  It also has switches for 
FACP Acknowledge, Silence, Reset and Drill.  It has rotary address switches and 
will accept up to three AEM-16AT Expanders
• AEM-16AT Annunciator Expander Module annunciates 16 zones with 16 red alarm 
LEDs and 16 yellow trouble LEDs
• ADT-AFM-16AT Annunciator Fixed Module annunciates 16 zones with 16 red 
alarm LEDs and 16 yellow trouble LEDs.  In addition, it has a System Trouble 
LED, an On Line/Power LED and a local piezo sounder.  It also has switches for 
FACP Acknowledge, Silence, Reset and Drill.  It is fixed at address ‘1’
• ADT-ACM-32A Annunciator Control Module annunciates 32 alarm zones with 32 
red LEDs.  In addition, it has a System Trouble LED, an On Line/Power LED and a 
local piezo sounder.  It also has a switch for local piezo silence.  It has rotary 
address switches and will accept one AEM-32A Expander
• AEM-32A Annunciator Expander Module annunciates 32 alarm zones with 32 red 
LEDs
• ADT-AFM-16A Annunciator Fixed Module annunciates 16 alarm zones with 16 
red alarm LEDs.  In addition, it has a System Trouble LED, an On Line/Power LED 
and a local piezo sounder.  It also has a switch for local piezo silence.  It is fixed at 
address ‘1’
• ADT-AFM-32A Annunciator Fixed Module annunciates 32 alarm zones with 32 
red LEDs
bb
-55f.cdr
Reference
Manual
Reference
Manual