Installation
Relays
28
Unimode 9600   PN 51336:C    11/06/01
2.3  Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C 
trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 
VAC (resistive).  The Alarm and Supervisory silk-screen labels reflect the factory default 
programming for the two programmable relays.
Note that relay connections may be power-limited or nonpower-limited, provided that 
0.25” spacing is maintained between conductors of power-limited and nonpower-limited 
circuits.  Refer to UL Power-limited wiring requirements.
2.4  Notification Appliance Circuits
The control panel provides two NAC (Notification Appliance Circuits) configurable for 
Style Y/Class B or Style Z/Class A.  Each circuit is capable of 3.0 amps of current.  Total 
system current cannot exceed 7.2 amps (refer to  "Calculating the System Current Draw" 
on page 128).  Use UL listed 24 VDC notification appliances only.  Circuits are supervised 
and power-limited.  Refer to the ADT Device Compatibility Document for a listing of 
compatible notification appliances.  The two NACs, which are located on the main circuit 
board, may be expanded via the FCPS Series field charger/power supplies.  Surge 
protection for notification appliances may be provided by using one of the UL listed 
compatible surge suppressors listed in the ADT Device Compatibility Document. 
ALARM
RELAY
NO
NC
NO
NC
NO
NC
C
C
C
SUPV
RELAY
TROUBLE 
RELAY
Figure 2.5 Relay Terminals
Relay contacts shown with power applied to panel and 
no active troubles, alarms or supervisories
TB5
Note that the relays labeled as Alarm 
Relay (Relay 1) and Supervisory Relay 
(Relay 3) reflect the factory default 
programming for these relays which are 
programmable.  
The relay labeled Trouble Relay (Relay 2) 
is fixed and cannot be changed.  It is a fail-
safe relay which will transfer on any 
trouble or total power failure.
9600r
eyp.cdr
Reference
Manual
See Page
+
+
B+ A+ A- B- B+ A+ A- B-
1     2     3   4    5     6    7    8
Figure 2.6 NAC Connections
Style Y (Class B) Notification Appliance Circuit, supervised 
and power-limited - 4.7 kohm, ½ watt P/N:71252 UL listed
Style Z (Class A) Notification Appliance Circuit, 
supervised and power-limited
Polarized Bell
Polarized Bell
Polarized Horn
Polarized Horn
Polarized Horn
Polarized Strobe
Notification Appliance Circuit 
polarity shown in alarm state
Dummy Load all unused circuit
TB4
+
+
+
9600nac
.cdr