Справочник Пользователя для System Sensor 1400

Скачать
Страница из 4
D400-07-00                                                                                              2                                                                                              I56-279-05R
Mounting
Each 1400 detector is supplied with a mounting bracket kit 
that permits the detector to be mounted:
1. Directly to a 3
1
2
 inch or 4 inch octagonal, 1
1
2
 inch deep 
electrical box, or
2. To a 4 inch square electrical box by using a plaster ring 
with the supplied mounting bracket kit.
Installation Wiring Guidelines
All  wiring  must  be  installed  in  compliance  with  the 
National Electrical Code and all applicable local codes and 
any special requirements of the authority having jurisdic-
tion,  using  the  proper  wire  size.  The  conductors  used  to 
connect  smoke  detectors  to  control  panels  and  accessory 
devices should be color-coded to reduce the likelihood of 
wiring errors. Improper connections can prevent a system 
from responding properly in the event of a fire.
For  signal  wiring  (the  wiring  between  interconnected 
detectors), it is recommended that the wire be no smaller 
than AWG 18. However, the screws and clamping plate can 
accommodate wire sizes up to AWG 12. The use of twisted 
pair wiring for the power (+ and –) loop is recommended 
to minimize the effects of electrical interference.
Smoke  detectors  and  alarm  system  control  panels  have 
specifications  for  allowable  loop  resistance.  Consult  the 
control  panel  manufacturer’s  specifications  for  the  total 
loop  resistance  allowed  for  the  control  panel  being  used 
before wiring the detector loops.
Begin electrical connections by stripping about 
3
8
″ insula-
tion from the end of the wire. Then, slide the bare end of 
the wire under the clamping plate and tighten the clamping 
plate screw. A wiring diagram for a typical 2-wire detector 
system is shown in Figure 3.
NOTE:  Break the wire at each terminal to ensure that the 
connections are supervised. Do NOT loop the wire 
under the terminals. 
System Sensor smoke detectors are marked with a compat-
ibility identifier located as the last digit of a five digit code 
stamped  on  the  back  of  the  product.  Connect  detectors 
only  to  compatible  control  units  as  indicated  in  System 
Sensor’s  compatibility  chart  which  contains  a  current  list 
of UL-listed control units and detectors. A copy of this list 
is available from System Sensor upon request.
Tamper-resistant Feature
This detector includes a tamper-resistant feature that effec-
tively prevents removal of the detector without the use of 
a  tool.  To  make  the  detector  tamper-resistant,  break  off 
the smaller tab at the scribed line on the tamper resistant 
tab, on the detector mounting bracket (see Figure 2), then 
install the detector. To remove the detector from the bracket 
once it has been made tamper resistant, use a small screw-
driver  to  depress  the  tamper-resistant  tab  located  in  the 
slot on the mounting bracket and turn the detector coun-
terclockwise for removal.
Installation
WARNING
Disconnect  the  power  to  the  alarm  system  control  unit 
before installing detectors.
1. Wire the detector following the installation guidelines.
2. Line up arrows on the detector with the arrows on the 
mounting bracket.
3. Rotate the detector clockwise until it clicks into place.
4.  After  all  detectors  have  been  installed,  apply  power  to 
the control unit.
5. Test the detector as described under TESTING.
6. Reset the detector at the system control panel.
7. Notify the proper authorities that the system is in opera-
tion.
S0139-00
TAMPER
RESISTANT
TAB
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
Figure  2. Model 1400 detector mounting bracket: 
Figure 1. Surface mounting of Model 1400 detector 
on 3-1/2 and 4 inch octagonal box:
S0140-00