Two LEDs on each duct smoke detector may light, if programmed by the 
system control panel, to provide a local, visible indication.  Remote LED 
annunciator capability is available as an option. Each duct smoke detector 
can only be wired to one remote accessory.
Different panel manufacturers offer different feature sets across their dif-
ferent panel models.  As a result, certain features of the DH200RPL may be 
available on some control panels, but not on others.  The possible features 
available in the DH200RPL, if supported by the control panel are:  
1.  Panel  controls  the  LED  operation  on  sensor.    Operational  modes  are 
RED blink, RED continuous, and off.  
2.  The remote output of the RA400Z does not follow the condition of the 
duct smoke detector LED while in standby. When in alarm, the LED 
output of the detector and remote will be identical.
Please refer to the operation manual for the UL 
listed control panel for specific operation of the DH200RPL.
Wiring Instructions
 
 
Disconnect power from the communication line before installing the 
DH200RPL duct smoke detector.  
Wire the DH200RPL duct smoke detector per the Control Panel Installation 
Manual and Figures 9, 10 or 11.
Set the desired address on the sensor board address code wheel switches 
(see Figure 7).
[7] Perform Detector Check 
1.  Perform STANDBY AND TROUBLE TEST per Section [9.2.1].
2.  Perform MAGNET TEST per Section [9.2.2.1]. The
     RTS451 test of Section [9.2.2.2] may substitute for this requirement.                                                                   
3.  Perform AIR FLOW TEST per Section [9.1].
4.  Perform SMOKE RESPONSE TEST per Section [9.1.1].
[8] Install The Cover 
Install  the  cover  using  the  six  screws  that  are  captured  in  the  housing 
cover. Be certain filters are installed as specified in Section [5]. Make sure 
that the cover fits into the base groove and that all gaskets are in their 
proper positions. Tighten the six screws.
[9] Duct Smoke Detector Maintenance and Test Procedures
Test and maintain duct smoke detectors as recommended in NFPA 72. The 
tests contained in this manual were devised to assist maintenance person-
nel in verification of proper detector operation. 
Before conducting these tests, notify the proper authorities that the smoke 
detection system will be temporarily out of service. Disable the device or 
system under test to prevent unwanted alarms.
D200-39-00                                                                                              4                                                                                          I56-1977-004R
NOTE:     Air  currents  inside  the  duct  may  cause  excessive  vibration, 
especially  when  the  longer  sampling  tubes  are  used.  In  these 
cases a 3 inch (75mm) floor flange (available at most plumb-
ing supply stores) may be used to fasten the sampling tube to 
the  other  side  of  the  duct.  When  using  the  flange/connector 
mounting  technique,  drill  a  1-inch  to  1
1
4
-inch  (25  to  32mm) 
hole where the flange will be used.
[5] Install The Filters
 
To install the sampling tube filters, simply push the filters into the sam-
pling and exhaust tube holes, as shown in Figure 6. If a metal sampling 
tube is used, install the filters into the tube end.
CAUTION
Filters require periodic cleaning or replacement, depending on the amount 
of dust and dirt accumulated. Visually inspect the filters at least quarterly; 
inspect them more often if the dust accumulation warrants it. See Section 
[9.1.2]  for  more  information.  Replacement  filters  can  be  ordered  (filter 
P/N F36-09-11).
[6] Field Wiring Installation Guidelines
All  wiring  must  be  installed  in  compliance  with  the  National  Electrical 
Code and the local codes having jurisdiction. Proper wire gauges should 
be  used.  The  conductors  used  to  connect  smoke  detectors  to  control 
panels  and  accessory  devices  should  be  color-coded  to  prevent  wiring 
mistakes.  Improper  connections  can  prevent  a  system  from  responding 
properly in the event of a fire.
For signal wiring, (the wiring between detectors or from detectors to auxil-
iary devices), it is usually recommended that single conductor wire be no 
smaller than 18 gauge. The duct smoke detector terminals accommodate 
wire sizes up to 12 gauge. The last foot (0.3m) of conduit should be flex-
ible conduit (available in electrical supply houses), which facilitates easier 
installation and puts less strain on the conduit holes in the housing. Solid 
conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for 
Signaling-Line Circuit (SLC) wiring. Consult the control panel manufactur-
er’s specifications for wiring requirements for the particular model control 
panel
 
being used before wiring the detector loop. 
The  DH200RPL  detector  is  designed  for  ease  of  wiring.  The  housing 
provides a terminal strip with clamping plates.  Wiring connections are 
made by stripping about 
3
8
-inch (9mm) of insulation from the end of the 
wire,  sliding  the  bare  end  under  the  plate,  and  tightening  the  clamping 
plate screw. 
Figure 6. Sampling tube filter installation:
Figure 7. Rotary Address Switches