I56-432-11R
DH500ACDC Intelligent Air Duct 
Smoke Detector Housing
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing
Please  thoroughly  read  the  System  Sensor  Manual  I56-
473-XX,  Guide  for  Proper  Use  of  Smoke  Detectors  in  Duct 
Applications
,  which  provides  detailed  information  on 
detector  spacing,  placement,  zoning,  wiring,  and  special 
applications.  Copies  of  this  manual  are  available  at  no 
charge  from  System  Sensor.  NFPA  Standards  72  and  90A 
should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user 
of this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
Specifications
Length: 
14.5 inches   
(36.7 cm.)
Width: 
5 inches 
 
(12.7 cm.)
Depth: 
4 inches 
 
(10.2 cm.)
Weight: 
4 lbs.  
(1.8 kg.)
Operating Temperature Range: 
32° to 120°F (0° to 49°C)
Operating Humidity Range: 
10% to 93% Relative Humidity
Duct Air Velocity: 
500 – 4000 ft./min. (91.4 – 1219.2 m/min.
Power Supply Electrical Ratings For DH500ACDC
The currents shown for the DH500ACDC are maximum values with no accessories.
* All accessory currents are additional to DH500ACDC. There are no additional currents for accessories in standby.
** RTS451/RTS451KEY when the magnet is held in place to initiate an alarm.
24V output maximum load is 80 mA; auxiliary alarm output maximum load is 20 mA.
Auxiliary Relay Contacts
Minimum contact current must be greater than 500 mA at 24 VDC 
 
10 amps maximum at 30 VDC
 
10 amps maximum at 250 VAC
General Description
An HVAC system supplies conditioned air to virtually every 
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense 
the presence of smoke in the duct.
The DH500ACDC Air Duct Detector Housings are used with 
System Sensor’s Model 1551 ionization detector heads and 
Model 2551 photoelectronic detector heads (purchased sep-
arately). These two smoke detection methods are  combined 
with  an  efficient  housing  design  that  samples  air  passing 
through a duct and allows detection of a developing hazard-
ous condition. When sufficient smoke is sensed, an alarm 
signal  is  initiated  at  the  fire  control  panel  monitoring  the 
detector,  and  appropriate  action  can  be  taken  to  shut  off 
fans  and  blowers,  change  over  air  handling  systems,  etc. 
This  can  prevent  the  distribution  of  toxic  smoke  and  fire 
gases throughout the areas served by the duct system.
Power
120 VAC (102 - 132)
240 VAC (204 - 264)
24 VAC (20.6 - 26.4)
24 VDC (20 - 30)
Requirements
mA rms MAX.
mA rms MAX.
mA rms MAX.
mA DC MAX.
  
Device
Standby
Alarm
Standby
Alarm
Standby
Alarm
Standby
Alarm
  
DH500ACDC
44
52
25
30
65
182
26
87
  
PA400*
--
3
--
1.5
--
29
--
15
  
RA400ZA*
--
1.5
--
1
--
17.3
--
10
  
RTS451/RTS451KEY*
--
1.5
--
1
--
17.3
--
10
  
RTS451**/RTS451KEY
11.5
13
5.5
6.5
140
157
95
103