Справочник Пользователя для Honeywell 25/50ZST
22
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
Product Description
Specifications
End-of-Line Resistor required for Class B using Terminals 1(+) & 4(-): 4.7 K
, ½ watt
(P/N: 27072)
Class A (no End-of-Line Resistor) requires the wiring of Terminal 1(+) to 2(+) and Terminal
3(-) to 4(-)
3(-) to 4(-)
Up to 25 Distributed Audio Panels may be connected to this output (ACC-25/50 Only)
Special Application Power (Aux. Power) - TB4 Terminals 1(+) & 2(-)
Up to 35 mA @ 24 VDC of special application power is available for powering addressable mod-
ules and associated End-of-Line power supervision relays.
ules and associated End-of-Line power supervision relays.
Power-limited circuitry. Refer to the Device Compatibility Document for a list of compatible
devices.
devices.
Form-C Trouble Relay - TB1
Normally energized fail-safe relay can be programmed to transfer its contacts on any panel trouble
condition or on any trouble condition except AC Loss (see Table 2.3 on page 34).
condition or on any trouble condition except AC Loss (see Table 2.3 on page 34).
TB1 Form-C relay contact rating: 2.0 amps @ 30 VDC (resistive), 0.6 amps @ 30 VAC (resistive).
External Audio Input
• RCA Audio Jack Input (female connector)
nput Impedance: 30K
maximum
Input Voltage: 700 mV
RMS
maximum
Input Current: 1 mA maximum @ 700 mV
Requires preamplifier output. Mates to an RCA phono 'plug' - 3mm diameter, 10mm
length, 9mm shell diameter.
Requires preamplifier output. Mates to an RCA phono 'plug' - 3mm diameter, 10mm
length, 9mm shell diameter.
• 3.5 mm PC Audio Jack Input (female connector)
Requires preamplifier output
Interfaces to personal computer line output
Interfaces to personal computer line output
FC-MIM Microphone Interface Module (Optional) - P5 Connector
Connector P5 provides a connection for:
• the optional FC-MIM Microphone Interface Module which is used to connect the FC-RM
Remote Microphone Module to provide remote microphone paging capabilities.
• the ACC-FFT Fire Fighter Telephone module which is used for emergency telephone appli-
cations.
Microphone connector for Fire•Lite standard microphone P/N:45025 - P6 Connector
ACC-EPM External Page Module (Optional)
ACC-EPM External Page Module (Optional)
Audio Input Impedance: 600
maximum
Audio Input Voltage: 700 mV
RMS
maximum
Audio Input Current: 1 mA maximum @ 700 mV
Contact Closure Operation Current: 2.3 mA maximum
External paging equipment is electrically isolated from ACC-25/50, ACC-25/50ZS and ACC-
25/50ZST
Contact Closure Operation Current: 2.3 mA maximum
External paging equipment is electrically isolated from ACC-25/50, ACC-25/50ZS and ACC-
25/50ZST
NOTE: Some laptop personal computers only provide an audio output for headphones. It may
be necessary to adjust the headphone output level for proper recording of voice messages.
be necessary to adjust the headphone output level for proper recording of voice messages.
NOTE: For systems that require both the Remote Microphone and Fire Fighter Telephone, the
ACC-FFT is connected to the P5 connector on the main circuit board and the Remote Microphone
connections are made on the ACC-FFT. The FC-MIM is incorporated into the ACC-FFT Fire
Fighter Telephone Module as part of the ACC-25/50ZST. A separate FC-MIM is therefore not
required for this system.
ACC-FFT is connected to the P5 connector on the main circuit board and the Remote Microphone
connections are made on the ACC-FFT. The FC-MIM is incorporated into the ACC-FFT Fire
Fighter Telephone Module as part of the ACC-25/50ZST. A separate FC-MIM is therefore not
required for this system.