14
MODEL 5081-P pH/ORP
SECTION 2.0
INSTALLATION
2.5 POwER SUPPLy/CURRENT LOOP 
—  MODEL 5081-P-HT
2.5.1  Power  Supply  and  Load  Requirements.
Refer to Figure 2-3.
The  minimum  power  supply  voltage  is  12.5  Vdc
and the maximum is 42.4 Vdc. The top line on the
graph  gives  the  voltage  required  to  maintain  at
least  12.5  Vdc  at  the  transmitter  terminals  when
the  output  signal  is  22  mA.  The  lower  line  is  the
supply voltage required to maintain a 30 Vdc ter-
minal voltage when the output signal is 22 mA.
The power supply must provide a surge current dur-
ing the first 80 milliseconds of start-up. For a 24 Vdc
power supply and a 250 ohm load resistor the surge
current  is  40  mA.  For  all  other  supply  voltage  and
resistance  combinations  the  surge  current  is  not
expected to exceed 70 mA.
For digital (HART or AMS) communications, the load must be at least 250 ohms. To supply the 12.5 Vdc lift off voltage at
the transmitter, the power supply voltage must be at least 18 Vdc.
For intrinsically safe operation the supply voltage should not exceed 30.0 Vdc.
2.5.2 Power Supply-Current Loop wiring.  Refer to Figure 2-4.
Run  the  power/signal  wiring  through  the
opening  nearest  terminals  15  and  16.  use
shielded cable and ground the shield at the
power  supply.  To  ground  the  transmitter,
attach the shield to the grounding screw on
the  inside  of  the  transmitter  case.  A  third
wire can also be used to connect the trans-
mitter case to earth ground.
NOTE
For  optimum  EMI/RFI  immunity,  the
power  supply/output  cable  should  be
shielded  and  enclosed  in  an  earth-
grounded metal conduit.
do  not  run  power  supply/signal  wiring  in
the  same  conduit  or  cable  tray  with  AC
power  lines  or  with  relay  actuated  signal
cables. Keep power supply/ signal wiring at
least 6 ft (2 m) away from heavy electrical
equipment. 
An  additional  0-1  mA  current  loop  is  avail-
able between TB-14 and TB-15. A 1 mA cur-
rent in this loop signifies a sensor fault. See
Figure  4-3  for  wiring  instructions.  See
Section  8.4  or  10.6  and  Section  12.0  for
more information about sensor faults.
FIGURE 2-3. Load/Power Supply Requirements
FIGURE 2-4. Model 5081-P-HT Power wiring Details