Water  supply  systems  may,  because  of  code  requirements  or  such 
conditions as high line pressure, among others, have installed devices 
such as pressure reducing valves, check valves, and back flow preventers. 
Devices such as these cause the water system to be a closed system.
therMal eXpansIon
As water is heated, it expands (thermal expansion). In a closed system 
the volume of water will grow when it is heated. As the volume of water 
grows  there  will  be  a  corresponding  increase  in  water  pressure  due 
to  thermal  expansion.  Thermal  expansion  can  cause  premature  tank 
failure  (leakage). This  type  of  failure  is  not  covered  under  the  limited 
warranty. Thermal expansion can also cause intermittent Temperature-
Pressure Relief Valve operation: water discharged from the valve due 
to excessive pressure build up. This condition is not covered under the 
limited warranty. The Temperature-Pressure Relief Valve is not intended 
for the constant relief of thermal expansion.
A properly sized thermal expansion tank must be installed on all closed 
systems to control the harmful effects of thermal expansion. Contact a 
local plumbing service agency to have a thermal expansion tank installed.
note: to protect against untimely corrosion of hot and cold 
water fittings, it is strongly recommended that di-electric 
unions or couplings be installed on this water heater when 
connected to copper pipe.
All gas piping must comply with local codes and ordinances or with the 
National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper and brass 
tubing and fittings (except tin lined copper tubing) should not be used.
fIGure 10.
cheMIcal vapor corrosIon
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF 
AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL VAPORS. SUCH 
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray  can  propellants,  cleaning  solvents,  refrigerator  and  air 
conditioning  refrigerants,  swimming  pool  chemicals,  calcium  and 
sodium chloride (water softener salt), waxes, and process chemicals 
are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is 
brought  in  contact  with  the  heater  should  not  contain  any  of  these 
chemicals. If necessary, uncontaminated air should be obtained from 
remote or outside sources. The limited warranty is voided when failure 
of water heater is due to a corrosive atmosphere (see limited warranty 
for complete terms and conditions).
water pIpInG
HOTTER  WATER  CAN  SCALD: 
Water heaters are intended to produce hot water. Water heated to a 
temperature  which  will  satisfy  space  heating,  clothes  washing,  dish 
washing, cleaning and other sanitizing needs can scald and permanently 
injure you upon contact. Some people are more likely to be permanently 
injured by hot water than others. These include the elderly, children, the 
infirm, or physically/mentally handicapped. If anyone using hot water in 
your home fits into one of these groups or if there is a local code or state 
law requiring a certain temperature water at the hot water tap, then you 
must take special precautions. In addition to using the lowest possible 
temperature setting that satisfies your hot water needs, a means such 
as a *mixing valve should be used at the hot water taps used by these 
people or at the water heater, see Figure 2. Valves for reducing point of 
use temperature by mixing cold and hot water are also available.
 
Consult a Qualified Installer or Service Agency. Follow  manufacturer’s 
instructions for installation of the valves. Before changing the factory 
setting on the thermostat, read the “Temperature Regulation” section 
in this manual.
This water heater should not be connected to any heating systems or 
component(s) used with a non-potable water heating appliance.
All  piping  components  connected  to  this  unit  for  space  heating 
applications should be suitable for use with potable water.
Toxic chemicals such as those used for boiler treatment, should not be 
introduced into this system.
When the system requires water for space heating at temperatures higher 
than required for domestic water purposes, a tempering valve must be 
installed. Please refer to Figure 2 for suggested piping arrangement.
InstallInG the new water heater