checking the firing rate
if  firing  rate  adjustment  is  required  follow  these  instructions  to 
determine the actual firing rate of the water heater:
1.  Ensure there are no other gas fired appliances connected to 
the gas meter firing during this test.
2.  Contact the gas supplier to determine the heating value, in 
Btu per cubic foot, of the gas supply.
3.  Connect  a  manometer  to  the  manifold  gas  pressure  tap. 
4.  Start the water heater and ensure it is firing.
5.  Check the manifold gas pressure, refer to Table 4 on page 14 
6.  Locate the gas meter serving the water heater.
7.  Time how long (in seconds) it takes for one cubic foot of gas 
to be used while the water heater is firing with a stop watch.
8.  Use the formula below to “clock” the gas meter and determine 
the actual firing rate of the water heater based on the heating 
value (Btu per cubic foot) of the gas supply:
x  H  =  Btu/hr
3600
T
x  1050  =  300,000 Btu/hr (87.9 kW)
3600
12.6
Example:
•  3600 = seconds in one hour.
•  T = time, in seconds, to burn one cubic foot of gas.
•  H = heating value of gas in Btu per cubic foot. 
•  Btu/hr = actual firing rate of the water heater.
note: 1050 Btu per cubic foot is a standard value for 
natural gas. Standard propane gas Btu content is 2500 
Btu per cubic foot. Btu values may change in certain 
areas and at high elevations. Check with the local gas 
utility company.
to turn off gas
1.  Change the Operating Set Point to the lowest temperature 
2.  When the water heater has completed its shut down sequence 
and enters the standby mode, turn the water heater’s on/off 
switch to the “off” position.
3.  Close the main Gas Shutoff Valve, see Figure 52 on page 39.
high altitude installations
Fire and Explosion Hazard
Gas and carbon monoxide detectors are
available.
Overfiring could result in fire or
explosion.
Under no circumstances should the 
input exceed the rate shown on the 
water heater’s rating label. 
              
Breathing Hazard - Carbon Monoxide Gas
Breathing carbon  monoxide can cause brain  damage or
death.  Always read and understand  instruction  manual.
Under no circumstances should
the input exceed the rate shown
on the water heater’s rating label. 
Overfiring could result in damage to
the water heater and sooting.
Gas and carbon monoxide detectors
are available.
SUF  100  120  and  SUF  100  150  models  are  certified  for  use 
without modification for altitudes up to 7,700 feet (2,347 m).
SUF  100  199  and  SUF  100  250  models  are  certified  for  use 
without modification for altitudes up to 10,100 feet (3,078 m).
most gas utility companies de-rate their gas for high altitudes, 
making it unnecessary to install high altitude orifices. 
For installations above the certified elevations listed above call 
the technical support phone number listed on the back cover of 
this manual for further technical assistance. Call the local gas or 
utility company to verify Btu per cubic foot content before calling 
for technical assistance and have that information available.
note: The actual firing rate of the water heater must not exceed 
the  input  rating  on  the  water  heater's  rating  label  under  any 
circumstances.
note:  Due  to  the  input  rating  reduction  at  high  altitudes,  the 
output  rating  of  the  appliance  is  also  reduced  and  should  be 
compensated for in the sizing of the equipment for applications.