Справочник Пользователя для State Industries GS675YRVLT

Скачать
Страница из 36
16
2.  A  venting  system  should  terminate  at  least  3  feet  above  any 
forced air inlet located within 10 feet.
3.  The venting system should terminate at least 4 feet below, 4 feet 
horizontally from or, 1 foot above any door, window or gravity air 
inlet  into any building.  
4.  The  manufacturer  also  recommends  that  the  vent  system 
termination  not  be  installed  closer  than  18”  from  an  inside 
corner of an L shaped structure and not be less than 1 foot 
above grade.  The vent should terminate a minimum of 12’’ 
above  expected  snowfall  level  to  prevent  blockage  of  vent 
termination.
5.  The vent termination should not be mounted directly above or 
within 3 feet horizontally from an oil tank vent or gas meter to 
avoid potential freeze-up from condensation.
Plan the vent system layout so that proper clearances are maintained 
from plumbing and wiring.
Vent  pipes  serving  power  vented  appliances  are  classified  by 
building codes as “vent connectors”.  Required clearances from 
combustible  materials  must  be  provided  in  accordance  with 
information in this manual under LOCATION OF HEATER and 
INSTALLATION OF VENT SYSTEM, and with the National Fuel 
Gas Code and local codes.
plannInG the vent sYsteM
Plan the route of the vent system from the discharge of the blower 
to the planned location of the vent terminal.
1.  Layout the total vent system to use a minimum of vent pipe and 
elbows.  Take into consideration that an elbow will be necessary 
to make the first vent pipe connection to the power venter outlet, 
see Figure 6.
2.  This  water  heater  is  capable  of  venting  the  flue  gases  the 
equivalent of thirty (30) feet of 3 inch pipe or one-hundred (100) 
feet of 4 inch pipe as listed in Table 1.
taBle 1.
 
number of 
3” Maximum 
4” Maximum
 
90° elbows 
pipe (feet) 
pipe feet
 
ONE (1) 
25 
92
 
TWO (2) 
20 
84
 
THREE(3) 
15 
76
 
FOUR (4) 
10 
68
 
FIVE (5) 
- - -  
60
  Minimum of one (1) elbow and 2 feet of straight pipe must be 
installed for 3” and 4” pipe.
  note:  The equivalent feet of pipe listed above are exclusive 
of    the  “45°  Elbow”  termination. That  is,  the  termination  “45° 
Elbow”, with installed screen, is assumed to be in the system 
and the remainder of the system must not exceed the thirty (30) 
equivalent feet of 3 inch pipe or one-hundred (100) equivalent 
feet of 4 inch pipe.
3.  The blower discharge adapter is made to accept only straight 
sections of 3” pipe. To start a minimum of 2 inches of 3” pipe 
must be attached to the blower discharge. See Figure 6.
  If using 3 inch vent pipe:
  A minimum of 2 inches, maximum of 4 feet of 3” pipe must be 
attached to the blower before the first 3-inch elbow.  After the first 
elbow add the additional venting required for the installation.  The 
total system cannot exceed 30 equivalent feet of venting, where 
each elbow is equal to 5 feet of straight pipe.
  If using 4 inch vent pipe:
  Two inches of 3” pipe must be attached to the blower discharge.  
A 4” x 3” reducer is added and then up to maximum 4 feet of 
4 inch pipe added before the first elbow.  An additional 4” x 3” 
reducer and (1) foot of 3” pipe must be added to the end of the 
vent system before terminating into the 3” 45° elbow.  The total 
system cannot exceed 100 equivalent feet of 4” venting, where 
each elbow is equal to 8 feet of straight pipe.
fIGure 15.
u.s. horIZontal vent clearances
 warnInG
vent hood(s) MaY Be
eXtreMelY hot 
durInG operatIon.