TABLE A – ELECTRICAL CHARACTERISTICS
INPUT
KW
NO. OF
ELEMENTS
ELEMENT
WATTAGE
FULL LOAD CURRENT
IN AMPERES
208 VOLTS
PHASE
1         3
240 VOLTS
PHASE
1         3
600 VOLTS
PHASE
1         3
9
3
3000
43
25
38
22
9
12
3
4000
58
33
50
29
12
15
3
5000
72
42
63
36
15
18
3
6000
87
50
75
43
18
24
6
4000
116
67
100
58
23
30
6
5000
144
84
125
73
29
36
6
6000
173
100
150
87
35
TABLE B – RECOVERY CAPACITIES
Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises
INPUT
EQUIVALENT
40°F
50°F
60°F
70°F
80°F
90°F
100°F
110°F 120°F 130°F 140°F
KW
BTU/HR.
UNITS
(22°C)
(28°C)
(33°C)
(39°C)
(45°C)
(50°C)
(56°C)
(61°C)
(67°C)
(72°C)
(78°C)
9
30,709
GPH
93
74
62
53
47
41
37
34
31
29
27
LPH
352
282
235
201
176
157
141
128
117
108
101
12
40,946
GPH
124
99
83
71
62
55
50
45
41
38
35
LPH
470
376
313
268
235
209
188
171
157
145
134
15
51,183
GPH
155
124
103
89
78
69
62
56
52
48
44
LPH
587
470
391
335
294
261
235
213
196
181
168
18
61,420
GPH
186
149
124
106
93
83
74
68
62
57
53
LPH
705
564
470
403
352
313
282
256
235
217
201
24
81,893
GPH
248
199
165
142
124
110
99
90
83
76
71
LPH
939
751
626
537
470
417
376
342
313
289
268
30
102,366
GPH
310
248
207
177
155
138
124
113
103
95
89
LPH
1174
939
783
671
587
522
470
427
391
361
335
36
122,839
GPH
372
298
248
213
186
165
149
135
124
115
106
LPH
1409
1127
939
805
705
626
564
512
470
434
403
SAMPLE SPECIFICATIONS 
(For Trade Reference Only)
Water Heater shall be Rheemglas Commercial Electric Model _____________ having an input of ________KW
and a recovery rate of ______________GPH at  a __________° temperature rise, and equipped for ________ volt,
________ phase operation. Tank shall be lined with a double coating of exclusive Rheemglas high temperature
glass formula and furnished with rigidly supported anode rods. Tank shall be designed for 150 PSI working pres-
sure and be approved-listed and constructed in accordance with Canadian Electrical Codes. Tank shall be com-
pletely insulated with R-Foam
®
Insulation having a minimum insulation factor of R-16. Water heater shall be
equipped with ”screw-in” immersion elements, surface thermostat, and manual reset high temperature limit control. Large
terminal block that accepts either CU or AL field connect wire, plus grounding screw for attaching an equipment grounding
conductor.
LIMITED WARRANTY
This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty
Information brochure for complete warranty information.