CONNECTIONS – ELECTRICAL 
 
The power supply to the water heater must not be switched on until the 
water heater is filled with water
 and a satisfactory megger reading is 
obtained. 
 
All electrical work and permanent wiring must be carried out by a qualified 
person and in accordance with the Standards Australia Wiring Rules 
AS/NZS 3000 and local authority requirements. 
 
The water heater must be directly connected to a 240 V 50 Hz mains power 
supply. The continuous power supply to the solar control unit and the timer 
must be on the same circuit. A weatherproof double pole isolating switch must 
be installed adjacent to and accessible from the solar storage tank in 
accordance with AS 5601. 
 
A flexible 20 mm conduit is required for the electrical cable to the solar storage 
tank. The conduit is to be connected to the unit with a 20 mm terminator. 
Connect the power supply wires directly to the terminal block, ensuring there 
are no excess wire loops inside of the cover. 
 
The terminal block on the solar storage tank has two active connections. One 
active wire (marked “A”) is required for the operation of the solar control unit 
and one active wire (marked “TIMER A”) is required for the operation of the gas 
boosting system. The gas boosting system is switched by the timer. 
 
Note: 
• 
It is essential the active to the solar control unit is not switched by the timer. 
• 
The timer is not weatherproof and must be installed indoors. It is 
recommended the timer be located in the kitchen or laundry or other 
location easily seen by the householder. 
 
Connect the hot sensor lead from the solar collectors, through the hole in the 
side of the air duct, to the hot sensor cable connector adjacent to the terminal 
block. Fit the strain relief grommet over the hot sensor lead and secure at the 
hole in the air duct. 
 
43