INSTALLATION 
17 
OUTDOOR INSTALLATION 
The water heater is to be installed at 
ground level on a concrete or brick 
plinth (fire proof base) and must stand 
vertically upright with the back of the 
water heater against an external wall 
or alternatively against a fireproof 
screen extending at least 500mm 
above, below and either side of the flue 
terminal. Failure to observe this 
precaution can cause problems in high 
wind areas. A secondary flue is not 
required. 
 
For outdoor models the following 
distances should be observed: 
• 
At least 500mm between the top of 
the water heater and the eaves. 
• 
At least 500mm (265) or 1500mm 
(275) horizontally between the 
water heater and the edge of any 
opening into the building. 
• 
At least 1000mm (265) or 1500mm 
(275) vertically from the top of the 
water heater to the bottom edge of 
an openable window. 
• 
At least 500mm measured 
horizontally along the wall between 
the water heater and a return wall 
or external corner. 
• 
At least 500mm clear of any 
combustibles.