CONNECTIONS – PLUMBING 
26 
GAS INLET 
The gas connection is made to the left hand side of the gas control. The pipe 
work must be cleared of foreign matter before connection and purged before 
attempting to light the water heater. An isolation valve and disconnection union 
must be used to allow servicing and removal of the water heater. Refer to the 
Gas Installations Standard AS 5601 for the correct pipe sizing. 
 
Warning:
 Always isolate the water heater before pressure testing the gas 
supply system. Disconnect the water heater after the isolating cock to prevent 
the risk of serious damage to the gas control. Warranty does not cover damage 
of any nature resulting from failure to observe this precaution. Refer to rating 
label for gas types and pressures. 
 
Ensure the gas line is also purged at the union of the gas control. If this 
procedure is not followed, a retry lockout (i.e. single flashes on control module) 
may result on initial start up. The HSI system has a flame sensing period of 
2.5 seconds from the time the gas valve opens. If the burner flame is not 
sensed during this period, a five minute waiting period follows so any unburnt 
gas can escape before a second and third burner ignition is automatically 
attempted. If the third attempt is also unsuccessful, the system enters the re-
ignition attempt lockout mode. The LED on the control module has a series of 
flashes to indicate this mode (refer to label on the access cover). The electrical 
supply to the water heater must be turned off and then on again, or the reset 
button on the control module must be pressed to allow further ignition attempts. 
 
Caution: 
valve casting may crack if the fittings are over tightened. Cracked valve 
castings are not covered under warranty. Damaged valves must be replaced. 
 
PIPE SIZES 
The pipe sizing for hot water supply systems should be carried out by persons 
competent to do so, choosing the most suitable pipe size for each individual 
application. Reference to the technical specifications of the water heater and 
local regulatory authority requirements must be made. 
 
RELIEF VALVE 
The temperature pressure relief valve is shipped in the plastic bag attached to 
the side of the water heater. The temperature pressure relief valve must be 
fitted before the water heater is operated. Before fitting the relief valve, make 
sure the probe has not been bent. Seal the thread with Teflon tape - never 
hemp. Make sure the tape does not hang over the end of the thread. 
 
Screw the valve into the correct opening 
page 
22
)
 leaving the valve outlet pointing downwards. Do not use a wrench on 
the valve body - use the spanner flats provided.