TEMPERATURE CONTROL 
44 
THERMOSTAT ADJUSTMENT 
The water heater is supplied with the thermostat preset at 70ºC. It will be 
necessary to adjust the thermostat temperature setting if another temperature 
is required. 
 
When adjusting the thermostat 
temperature it is necessary to alter the 
thermostat offset. The table outlines the 
thermostat temperature and the 
corresponding offset. Failure to adjust 
the offset will result in incorrect water 
temperature.
 
 
To adjust the thermostat setting and offset: 
1.  Press the down button (▼) for five (5) seconds. The current set point value 
will be displayed. 
2.  Press the down button (▼) to decrease the set point or the up button (▲) to 
increase the set point. 
3. Once the required temperature is selected press and hold the down 
button (▼) and the up button (▲) simultaneously. The display will revert to 
the current temperature in the water heater. 
4.  Press and hold the down button (▼) and the up button (▲) simultaneously 
for ten (10) seconds, “C0” (offset program) will be displayed. Release the 
buttons. 
5.  Press and hold the down button (▼) and the up button (▲) simultaneously 
again. The current setting for “C0” will be displayed. Release the buttons. 
6.  Press the down button (▼) to decrease the setting or the up button (▲) to 
increase the setting according to the table, i.e. if the temperature set in step 
three is 60 then the offset value will be 14. 
7.  Once the required offset is selected press and hold the down button (▼) 
and the up button (▲) simultaneously, “C0” will be displayed. 
8.  Press the down button (▼) once; “EP” (exit program) will be displayed. 
9.  Press and hold the down button (▼) and the up button (▲) simultaneously; 
the current temperature in the water heater will now be displayed and 
programming complete. 
Note:
 During the programming process if a button is not pressed for 25 
seconds the thermostat will revert to its previous temperature display. It will be 
necessary to start again from step 1. 
Temperature Offset 
60 14 
65 15 
70 16 
75 17 
80 18 
82 * 
18 
* Recirculation required for 82
°C setting