Справочник Пользователя для Rinnai REU-VA3237FFU

Скачать
Страница из 44
 
26 
VA Series Indoor LS Manual 
  Venting 
Instructions      
 
 
 
 
 
 
 
 
 
 
 
 
This water heater is a direct vent water heater and 
therefore is certified and listed with the vent 
system.  You must use vent components that are 
certified and listed with the water heater model. 
Do not combine vent components from different 
manufacturers. 
The vent system must vent directly to the outside 
of the building and use outside air for combustion. 
Every vent connection must be accessible for 
inspection, cleaning, and replacement. 
Avoid dips or sags in horizontal vent runs by 
installing supports per the vent manufacturer
,
instructions. 
Support horizontal vent runs every four feet and all 
vertical vent runs every six feet or in accordance 
with local codes. 
Venting should be as direct as possible with a 
minimum number of pipe fittings. 
Vent diameter must not be reduced. 
Do not connect the venting system with an existing 
vent or chimney. 
Do not common vent with the vent pipe of any 
other water heater or appliance. 
Vent connections must be firmly pressed together 
so that the gaskets form an air tight seal. 
R50LSi, R75LSi, R94LSi: The vent piece 
connected to the water heater must be secured with 
one self-tapping screw. 
Refer to the vent pipe manufacturers
,
 instructions 
for component assembly instructions. 
Condensate  
Condensate formation can occur in high efficiency 
direct vent appliances.  To prevent condensate 
damage follow these instructions. 
Intake / Exhaust Guidelines 
Refer to the specific instructions on your vent 
product for additional installation requirements. 
Vertical terminations must incorporate a condensate 
drain and trap as close as possible to the appliance. 
The condensate trap must contain a minimum of 3 
inches (75 mm) of water. 
Dispose of condensate per local codes. 
Rinnai offers a condensate trap. 
Rinnai LSi tankless water heaters have an integrated 
condensate collector.
Slope any horizontal venting 1/4 inch per foot 
(19 mm / m), towards the heater if the condensate 
collector is used, or towards the exhaust terminal if 
the condensate collector is not used.
Regions of cold climate will create more condensate 
in the vent system.  The condensate collector should 
be used in cold climates.
NOTICE 
Provisions must be made to prevent the condensate 
from entering the water heater.  Without proper 
drainage or disposal condensate will damage the heat 
exchanger. 
     WARNING 
If the condensate collector is not used, the drain pipe 
must be capped to prevent exhaust gases and 
condensate from entering the building.  The cap is 
supplied on the appliance.