CONNECTIONS – PLUMBING 
25 
RELIEF VALVE DRAIN 
A copper drain line must be fitted to the relief valve to carry the discharge clear 
of the water heater. Connect the drain line to the relief valve using a 
disconnection union. The pipe work from the relief valve to the drain should be 
as short as possible and fall all the way from the water heater with no 
restrictions. It should have no more than three right angle bends in it. Use 
DN20 pipe. 
 
The outlet of the drain line must be in such a position that flow out of the pipe 
can be easily seen (refer to AS/NZS 3500.4) - but arranged so hot water 
discharge will not cause injury, damage or nuisance. The drain line must 
discharge at an outlet or air break not more than 9 metres from the relief valve. 
 
 