63230-300-212
Chapter 5—Input/Output Capabilities
April 2001
Analog Inputs
73
© 2001 Schneider Electric All Rights Reserved
Depending on the I/O modules you select, the circuit monitor can accept
either voltage or current signals through its analog inputs. See Table 5–1 on
page 70 
for a list of I/O options. The circuit monitor stores a minimum and a
maximum value for each analog input.
For technical specifications and instructions on installing I/O modules, refer
to the instruction bulletin that ships with the I/O (see Table 1–2 on page 3 for
a list of these publications). To set up analog inputs, you must first set it up
from the display. From the main menu, select Setup > I/O, then select the
appropriate analog input option. For example, if you are using the
IOX0404
option of the I/O Extender, select IOX-0404. For detailed instructions, see
“Setting Up I/Os” on page 23 in
. Then, in
SMS
define
the following values for each analog input:
Name
—a 16-character label used to identify the analog input.
Units—
the units of the monitored analog value (for example, “psi”).
Scale factor
—multiplies the units by this value (such as tenths or
hundreths).
Report Range Lower Limit
—the value the circuit monitor reports when
the input reaches a minimum value. When the input current is below the
lowest valid reading, the circuit monitor reports the lower limit.
Report Range Upper Limit
—the value the circuit monitor reports when
the input reaches the maximum value. When the input current is above
highest valid reading, the circuit monitor reports the upper limit.
For instructions on setting up analog inputs in
SMS
, see device set up of the
circuit monitor in the
SMS
online help.
ANALOG INPUTS