Справочник Пользователя для Honeywell TH8320

Скачать
Страница из 40
VisionPRO
TM 
8000 Touchscreen Programmable Thermostat
19
68-0280—01
0650
Extended Fan OnTime 
Heat
0—no extended fan operation after call for heat ends
90— fan operation is extended 90 seconds after call for 
heat ends.
Not shown if fan operation 
is set to fossil fuel or in 
Cool Only Systems
0660
Extended Fan On Time 
Cool
0—no extended fan operation after call for cool ends
90—fan operation is extended 90 seconds after call for 
cool ends.
Not shown in Heat Only 
Systems.
0670
Keypad Lockout
0—unlocked keypad
1—partially locked keypad                                              
2—fully locked keypad
Unlocked—all functions 
are available.
Partially locked—only 
temperature up and down 
keys and ability to enter 
and modify Installer Setup 
mode are available.                                  
Fully locked—only ability 
to enter and modify 
Installer Setup mode are 
available.
0680
Temperature Control in 
Heat
1—less aggressive temperature control (could cause 
temperature undershoot) 
2—Standard temperature control in heating (factory 
setting)
3—more aggressive temperature control (could cause 
temperature overshoot)
Applies to recovery ramp 
and use of auxiliary heat 
during recovery.
Choose 1 if getting 
temperature overshoot.
Choose 3 if getting 
temperature undershoot.
0690
Temperature Control in 
Cool
1—less aggressive temperature control (could cause 
temperature undershoot)   
2—Standard temperature control in cooling 
(factory setting)
3—more aggressive temperature control (could cause 
temperature overshoot)
Applies to recovery ramp.
Choose 1 if getting 
temperature overshoot.
Choose 3 if getting 
temperature undershoot.
0700
Temperature Display 
Offset
-3  —
°
F (-1.5
°
C)                                                                                    
-2 —°F (-1°C)                                                                              
-1 —°F (-.5°C)                                                                               
0 —°F (0. °C) — (no difference in displayed temperature  
and  actual  room  temperature  )                                                                            
1 —°F (.5°C)                                                                                
2 —°F (1°C 
3 —°F (1.5°C)
 —
0710
Reset Thermostat
0—no thermostat reset.
1—resets all Installer Setup Options to default values and 
resets schedule to default setting. 
Only calendar settings 
and time are retained.
Table 3. Installer Setup Menu. (Continued)
Installer Setup 
Number
Installer Setup Name
Settings
Notes