Справочник Пользователя для Lux Products RS4000

Скачать
Страница из 29
Pop-Up Wizard Configuration Chart
Displayed
Choice
Default
SCAL
F
°
 
or C
°
F
°
CLOC
12 or 24 hour
12
LITE
1=always on, 0=off
0
DIFF
Set Differential, 0.5-3 F
°
 
or 0.5-1.5 C
°
1 F
°
DIF2*
Set 2
nd 
Stage Differential, 1-6 F
°
 
or 0.5-3 C
°
2 F
°
DLY2*
2
nd 
stage time delay, 5-40 min
20
DLY3**
3
rd 
stage time delay, 5-40 min
20
AUTO
Enable Auto change over, Y = Yes, N = No 
Y
DEDB
Deadband in Degree’s, 1 – 8 F
°
3 F
°
HI
Upper heating limit, 45-90 F
°
90 F
°
LO
Lower Cooling Limit, 45-90 F
°
45 F
°
VAC HEAT***
Vacation Heating Set point, 45-90 F
°
60 F
°
VAC COOL***
Vacation Cooling Set point, 45-90 F
°
85 F
°
CHECK
Filter Monitor, hours, OFF – 9900
OFF
CYCL
Compressor Short Cycle Delay, minutes, 0 – 5
5
CAL
Temperature Calibration Offset, - 3 to 3 F
°
0