Справочник Пользователя для American Water Heater 318935-003

Скачать
Страница из 36
16
Water Heater Location
Water heater location is important and can affect system 
performance. Please check the following:
   Installation area free of corrosive elements and 
flammable materials.
   Centrally located with the water piping system. 
Located as close to the gas piping and vent pipe 
system as possible.
   Located indoors and in a vertical position. Protected 
from freezing temperatures.
   Proper clearances from combustible surfaces 
maintained and not installed directly on a carpeted 
floor.
   Provisions made to protect the area from water 
damage. Metal drain pan installed and piped to an 
adequate drain.
   Sufficient room to service the water heater. See 
“Clearances and Accessibility” section of this 
manual.
   Water heater not located near an air moving device.
  Is the installed environment dirty (excessive 
amounts of lint, dirt, dust, etc.)?  If so, the flame 
arrestor located on the bottom of the water heater 
will need to be cleaned periodically.  Refer to the 
“Maintenance of your Water Heater” section of this 
manual for information on cleaning the flame-trap. 
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply.  Insufficient air 
for the combustion of gas will result in the flame becoming 
“lazy”, thereby allowing the burner operating temperature 
to decrease.  This causes the gas control to shut off the 
gas supply. Is the water heater installed in a closet or other 
small, enclosed space? If so:
  Are there openings for make-up air to enter and 
exit the room/area? 
□ 
Are the openings of sufficient size?  Remember, 
if there are other gas-fired or air-consuming 
appliances in the same room, you need more 
make-up air.  Refer to the “Location Requirements” 
section of this water heater manual for specific 
requirements.
Fresh air not taken from areas that contain negative 
pressure producing devices such as exhaust fans, 
fireplaces, etc.
   Is there a furnace/air handler in the same room 
space as the water heater?  If so, has a return air 
duct system been attached that exits the room? 
If so, check for leaks on the air duct system. If no 
air duct system is present, correct immediately 
by contacting a local Heating, Ventilation, Air-
Conditioning & Refrigeration (HVAC-R) authorized 
service provider. 
   Fresh air supply free of corrosive elements and 
flammable vapors.
   Fresh air openings sized correctly with consideration 
given to the blocking effect of louvers and grilles.
   Ductwork is the same cross-sectional area as the 
openings.
Vent Pipe System
Check for proper drafting at the water heater draft hood. 
Refer to the “Checking the Draft” section of this manual for 
the test procedure. If the procedure shows insufficient draft 
is present, please check the following.
   Draft hood properly installed.
   Vent connectors securely fastened with screws and 
supported properly to maintain six inch clearance.
   Vent connector made of approved material and 
sized correctly.
   Vent pipe system installed according to all local 
and state codes or, in the absence of local and 
state codes, the “National Fuel Gas Code”, ANSI 
Z223.1(NFPA 54)-current edition.
   Flue baffle properly positioned in the flue tube.
   Check the vent system for restrictions/obstructions 
and check the vent termination height.  Refer to the 
“Air Supply and Ventilation” section of this water 
heater manual for specific requirements.
□  
Recheck for sufficient combustion air supply.
Water System Piping
   Temperature and pressure relief valve properly 
installed with a discharge line run to an open drain 
and protected from freezing.
   All piping properly installed and free of leaks.
   Heater completely filled with water.
   Closed system pressure build-up devices installed.
   Mixing valve (when applicable) installed per 
manufacturer’s instructions (see “Water Temperature 
Regulation” section).
Gas Supply and Piping
  Gas type is the same as that listed on the water 
heater data plate.
   Gas line equipped with shut-off valve, union, and  
drip leg.
   Adequate pipe size and approved pipe material.
   An approved noncorrosive leak detection solution 
used to check all connections and fittings for possible 
gas leaks. If such a solution is not available, use a 
mixture of dish washing soap and water (one part 
soap to 15 parts water) or children’s soap bubble 
solution. Bubbles forming indicate a leak. Correct 
any leak found.
TEFLON 
®
 is a registered trademark of E.I. Du Pont De Nemours and Company.
Important Information About This Water Heater
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor 
ignition incident. The new technology used in meeting these standards makes this product more sensitive to installation 
errors. Please review the following checklist and make any required installation upgrades or changes. 
Questions? Reference the number on the cover of this manual for service information.
Installation Checklist