Chapter 10 Mechanical Installation
10-4
Installation Manual
308014EN, Edition 4
May 2013
10.1.4 Installation on the tank
Follow this Step by Step instruction when installing the Cone Antenna 
Gauge.
Note!
When determining the dimensions for conduits (if used), note that the 
Horn Antenna Gauge may be inclined 4° towards the center of the tank. 
See Figure 10-2. Use flexible conduits close to the Radar T
ank Gauge. 
1
Check that all parts and tools 
are available before carrying 
them up to the tank top.
2
Carefully insert the horn and 
flange assembly into the socket. 
Tighten the flange onto the 
socket by using customer sup-
plied screws and nuts. Check 
that the socket height is less 
than 330 mm.
3
Mount the Waveguide Unit into 
the base of the Transmitter 
Head. On one end of the Wave-
guide Unit there are two screws 
with washers fitted. Mount the 
Waveguide Unit with this end 
first into the base of the Trans-
mitter Head. Enter the stop 
screws and tighten them.
Horn and flange assembly
Gasket (Customer supplied)
Customer supplied 
flange
Cone_pict1.eps
Socket
W11
W12
FOR
INTRINSICALLY
SAFE CIRCUITS
ONLY
"i"
Waveguide unit
M6 stop screw
Transmitter head
Cone_pict2.eps