Справочник Пользователя для Mitsubishi Electronics A951GOT

Скачать
Страница из 124
3 - 8
3.3 Power Supply Specifications
 
3.3 Power Supply Specifications
Remark
When an instantaneous power failure occurs for the time exceeding the permissible 
instantaneous power failure time in the 24VDC power supply, the GOT may be reset. 
In such a case, the GOT will automatically return and start communicating.
As the communication between the GOT and PLC is stopped when an instantaneous 
power failure occurs, some object functions may not be performed normally.
Item
Specifications
A950GOT, A951GOT-Q, A951GOT, A953GOT
A956GOT
A956WGOT
Input power supply voltage
24VDC (+10%, -15%)
Input max. power
12W
16W
22W
Inrush current
40Ap, max. (26.4VDC, max. load)
Permissible instantaneous power failure time
1 ms (19.2VDC or more)
Noise immunity
By noise simulator of 500Vp-p noise voltage, 1_s noise width and 25 to 60Hz noise frequency
Dielectric withstand voltage
500VAC for 1 minute across DC external terminals and earth
Insulation resistance
10M
 or larger by insulation resistance tester
Applicable wire size
0.75 to 2 mm
2
Applicable solderless terminal
RAV1.25-3, V2-S3.3,V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
59 to 88 N cm
2