Справочник Пользователя для Mitsubishi Electronics MR-J2S- A

Скачать
Страница из 385
12 -  8
12. CHARACTERISTICS
12.5 Inrush currents at power-on of main circuit and control circuit
The following table indicates the inrush currents (reference value) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.
Inrush Currents (A
0-p
)
Servo Amplifier
Main circuit power supply (L
1
, L
2
, L
3
)
Control circuit power supply (L
11
, L
21
)
MR-J2S-10A 20A
30A (Attenuated to approx. 5A in 10ms)
MR-J2S-40A 60A
30A (Attenuated to approx. 5A in 10ms)
MR-J2S-70A 100A
54A (Attenuated to approx. 12A in 10ms)
70 to 100A
(Attenuated to approx. 0A in 0.5 to 1ms)
MR-J2S-200A 350A
120A (Attenuated to approx. 12A in 20ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
MR-J2S-500A
44A (Attenuated to approx. 20A in 20ms)
MR-J2S-700A
88A (Attenuated to approx. 20A in 20ms)
MR-J2S-11KA
MR-J2S-15KA
MR-J2S-22KA
235A (Attenuated to approx. 20A in 20ms)
30A
(Attenuated to approx. 0A in several ms)
MR-J2S-10A1 20A1
59A (Attenuated to approx. 5A in 4ms)
MR-J2S-40A1
72A (Attenuated to approx. 5A in 4ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to Section 13.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped
by an inrush current.