13. OPTIONS AND AUXILIARY EQUIPMENT
13.2.8 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier,
servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current   10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(13.2)
K: Constant considering the harmonic contents
Leakage current breaker
Type
Mitsubishi
products
K
Models provided with
harmonic and surge
reduction techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-L
1
General models
BV-C1
NFB
NV-L
3
M
Servo  
amplifier
Noise  
filter
NV
Ig1 Ign
Iga
Ig2
Igm
Cable
Cable
Ig1: 
Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 13.1.)
Ig2: 
Leakage current on the electric channel from the output terminals of the servo amplifier to the 
servo motor (Found from Fig. 13.1.)
Ign: 
Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga: 
Leakage current of the servo amplifier (Found from Table 13.6.)
Igm: 
Leakage current of the servo motor (Found from Table 13.5.)
Table 13.5 Servo motor's
leakage current
example (Igm)
Table 13.6 Servo amplifier's
leakage current
  example (Iga)
Servo motor
output [kW]
Leakage
current [mA]
Servo amplifier
capacity [kW]
Leakage
current [mA]
0.05 to 0.5
0.1
0.1 to 0.6
0.1
0.6 to 1.0
0.1
0.7 to 3.5
0.15
1.2 to 2.2
0.2
5 7
2
3 to 3.5
0.3
11 15
5.5
5
0.5
22
7
7
0.7
Table 13.7 Leakage circuit breaker selection example
11
1.0
15
1.3
22
2.3
Servo amplifier
Rated sensitivity
current of leakage
circuit breaker [mA]
MR-J2S-10A to MR-J2S-350A
MR-J2S-10A1 to MR-J2S-40A1
15
MR-J2S-500A
30
MR-J2S-700A
50
120
100
80
60
40
20
0
2 3.5
5.5
8 1422 38 80 150
30 60 100
Fig. 13.1 Leakage current example 
               (Ig1, Ig2) for CV cable run  
               in metal conduit
Cable size[mm
2
]
 
[mA]
Le
a
k
ag
e
 cu
rr
e
n
t
MR-J2S-11KA to MR-J2S-22KA
100