6.7.5 Single-step feed 
POINT 
 
In the jog operation mode, do not rewrite data from the point table list 
screen or the servo amplifier's front panel. Otherwise, the set values are 
made invalid. 
The servo motor will not operate if the forced stop (EMG), forward 
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off. 
Make automatic ON setting to turn on these devices or make device 
setting to assign them as external input signals and turn ON across these 
signals and SG. (Refer to section 6.6.) 
 
Operation is performed in accordance with the preset point table No. 
Click “Test” on the menu bar and click “Single-step Feed” on the menu. 
 
When the above choices are made, the following window appears. 
b)
c)
d)
a)
 
 
(1) Point table No. setting ( a) ) 
Enter the point table No. into the “Point table No.” input field and press the enter key. 
 
(2) Servo motor start ( b) ) 
Click the “Start” button to rotate the servo motor. 
 
(3) Temporary stop of servo motor ( c) ) 
Press the “Pause” button to stop the servo motor temporarily. 
Click the “Start” button to resume rotation. 
 
(4) Servo motor stop ( d) ) 
Click the “Pause” button again during a temporary stop of the servo motor to clear the remaining 
moving distance. 
 
(5) Single-step feed window closing ( e) ) 