4. SIGNALS AND WIRING 
 
4.3.2 Power-on sequence 
(1) Power-on procedure 
1) Always wire the power supply as shown in above section 4.1 using the magnetic contactor with the 
main circuit power supply (three-phase: L
1
, L
2
, L
3
, single-phase: L
1
, L
2
). Configure up an external 
sequence to switch off the magnetic contactor as soon as an alarm occurs. 
 
2) Switch on the control circuit power supply L
11
, L
21
 simultaneously with the main circuit power supply 
or before switching on the main circuit power supply. If the main circuit power supply is not on, the 
display shows the corresponding warning. However, by switching on the main circuit power supply, 
the warning disappears and the servo amplifier will operate properly. 
 
3) The servo amplifier can accept the servo-on (RYn0) about 1 to 2s after the main circuit power supply 
is switched on. Therefore, when servo-on (RYn0) is switched on simultaneously with the main circuit 
power supply, the base circuit will switch on in about 1 to 2s, and the ready (RD) will switch on in 
further about 5ms, making the servo amplifier ready to operate. (Refer to paragraph (2) in this 
section.) 
 
4) When the reset (RY(n+1)A or RY(n+3)A) is switched on, the base circuit is shut off and the servo 
motor shaft coasts. 
 
(2) Timing chart 
95ms
95ms
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
10ms
5ms
10ms
10ms
5ms
10ms
5ms
10ms
(2 to 2.5s)
Servo-on (RYn0) accepted
Main circuit
Control circuit
Power supply 
Base circuit
Servo-on 
(RYn0)
Reset 
(RY(n+1)A 
or RY(n+3)A)
Ready 
(RD)
Power-on timing chart