5. OPERATION 
 
5.8 Absolute position detection system 
CAUTION 
If an absolute position erase alarm (A25) or an absolute position counter warning 
(AE3) has occurred, always perform home position setting again. Not doing so 
may cause unexpected operation. 
 
POINT 
 
If the encoder cable is disconnected, absolute position data will be lost in the 
following servo motor series. HF-MP, HF-KP, HC-SP, HC-RP, HC-UP, HC-
LP, and HA-LP. After disconnecting the encoder cable, always execute home 
position setting and then positioning operation. 
When the following parameters are changed, the home position is lost when 
turning on the power after the change. Execute the home position return 
again when turning on the power. 
Parameter No.PA06 (Electronic gear numerator) 
Parameter No.PA07 (Electronic gear denominator) 
Parameter No.PA14 (Rotation direction selection) 
Parameter No.PC07 (Home position return position data) 
 
This servo amplifier contains a single-axis controller. Also, all servo motor encoders are compatible with an 
absolute position detection system. Hence, an absolute position detection system can be configured up by 
merely loading an absolute position data back-up battery and setting parameter values. 
 
(1) Restrictions 
An absolute position detection system cannot be built under the following conditions. 
 
1) Stroke-less coordinate system, e.g. rotary shaft, infinite positioning. 
 
2) Operation performed in incremental value command type positioning system. 
 
(2) Specifications 
 
Item Description 
System 
Electronic battery backup system. 
Battery 
1 piece of lithium battery ( primary battery, nominal   3.6V) 
Type: MR-J3BAT. 
Maximum revolution range 
Home position   32767 rev. 
(Note 1) Maximum speed at power failure 
3000r/min 
(Note 2) Battery backup time 
Approx. 10,000 hours (battery life with power off) 
Battery storage period 
5 years from date of manufacture. 
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like. 
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years 
independently of whether power is kept on or off.