3. CC-LINK COMMUNICATION FUNCTIONS 
 
3.3 Functions 
3.3.1 Function block diagram 
This section explains the transfer of I/O data to/from the servo amplifier in CC-Link, using function blocks. 
 
(1) Between the master station and servo amplifier in the CC-Link system, link refresh is normally performed at 
intervals of 3.5 to 18ms (512 points). The link scan time of link refresh changes with the communication 
speed. For details, refer to the CC-Link system master/local unit user's manual. 
 
(2) The I/O refresh and master station sequence program are executed asynchronously. Some programmable 
controllers allow link scans to be synchronized with programmable controller scans. 
 
(3) The FROM instruction from the buffer memory of the CC-Link system master/local unit is used to read data 
from the servo amplifier, and the TO instruction is used to write data. Some programmable controllers allow 
automatic refresh to be set to omit the FROM and TO instructions. 
1) QJ61B11N
    I/O signal
CPU
Buffer
memory
2) Buffer memory access
3) CC-Link 
Ver.1.10-
compliant 
cable
Input
Output
Servo amplifier
CC-
Li
nk int
er
face
CC-Link int
erf
ac
e
S
ervo a
m
pli
fier CP
U
P
rogram
m
able co
nt
roller
CPU
In
te
rf
ace wit
h
program
m
able c
on
troller
Programmable controller
CC-Link unit
 
3.3.2 Functions 
The following table lists the functions that may be performed from the programmable controller in the CC-Link 
system in the CC-Link operation mode or test operation mode. 
 
Operation mode 
Item 
CC-Link operation mode 
Test operation mode 
Monitor 
 
 
Operation 
 
 
Parameter write 
 
 
Parameter read 
 
 
Point table data write 
 
 
Point table data read