11
                                                                  Table B.  24 VAC Wiring Distances
The following are the recommended maximum distances for 24 VAC with a 10-
percent voltage drop. (Ten percent is generally the maximum allowable voltage drop
for AC-powered devices.)
Wire Gauge
20
18
16
14
12
10
30 vA
94 ft
150 ft
238 ft
380 ft
603 ft
960 ft
(28 m)
(45 m)
(72 m)
(115 m)
(183 m)
(292 m)
75 vA
37 ft
60 ft
95 ft
152 ft
241 ft
384 ft
(11 m)
(18 m)
(29 m)
(46 m)
(73 m)
(117 m)