5.0 power Requirements
Sundance® spas are designed to provide optimum performance and
flexibility of use when connected to the maximum electrical service listed
in the tables below. If you prefer, your dealer can perform a minor circuit
board modification to allow your spa to accept an electrical service other
than the factory setting.
flexibility of use when connected to the maximum electrical service listed
in the tables below. If you prefer, your dealer can perform a minor circuit
board modification to allow your spa to accept an electrical service other
than the factory setting.
US/Canada Denali/Tacoma 1-pump Convertible models (60Hz)
120V/15A*
240V/30A*
240V/40A**
Voltage:
20 VAC
240 VAC
240 VAC
# of Wires:
3 (5A GFCI Cord -
4 (Hard
4 (Hard
US Models Only*)
Wired Only)
Wired Only)
Frequency:
60Hz
60Hz
60Hz
Current Draw:
2A
2A
30A
Circuit Breaker:
5A, -Pole
30A, 2-Pole
40A, 2-Pole
For 240 VAC Heater Operation: Move the red wire on the main terminal
strip (TB) from position # to position #3. Make certain wires are connected
exactly as shown in Figure-D (page 3) before applying power. Failure to do
so will result in damage to the circuit board and/or related components and
void the manufacturer’s warranty.
strip (TB) from position # to position #3. Make certain wires are connected
exactly as shown in Figure-D (page 3) before applying power. Failure to do
so will result in damage to the circuit board and/or related components and
void the manufacturer’s warranty.
* In the 5A/30A configuration, the heater will not operate at the same
time as the high-speed jets pump. The factory setting is 120V/15A.
Note: all Canadian spas must be hard wired (120 VAC or 240 VAC)
per CSA Canadian standards (page 4).
** If the spa is to be operated on 40A service, remove the jumper JP
#-2 on the circuit board to allow the heater to operate at the same time
as the high-speed jets pump (page 35).
time as the high-speed jets pump. The factory setting is 120V/15A.
Note: all Canadian spas must be hard wired (120 VAC or 240 VAC)
per CSA Canadian standards (page 4).
** If the spa is to be operated on 40A service, remove the jumper JP
#-2 on the circuit board to allow the heater to operate at the same time
as the high-speed jets pump (page 35).
US/Canada Burlington 2-pump models (60Hz)
240V/50A*
240V/40A**
Voltage:
240 VAC
240 VAC
# of Wires:
3
3
Frequency:
60Hz
60Hz
Current Draw:
36A
26A
Circuit Breaker:
50A, 2-Pole
40A, 2-Pole
* In 50A configuration, the heater will not operate while both jets pumps
are running in high speed. Note: pump 2 runs only in high speed. This is
the factory setting.
** In 40A configuration, the heater will not operate while either jets pump is
running in high speed. Note: pump 2 runs only in high speed.
are running in high speed. Note: pump 2 runs only in high speed. This is
the factory setting.
** In 40A configuration, the heater will not operate while either jets pump is
running in high speed. Note: pump 2 runs only in high speed.