CHAPTER 5:  Configuration
 
59
5.6.4.  Deleting Plug Groups
This function is used to delete individual Plug Groups.  Note that this function 
is only available when you have accessed command mode using a password that 
permits Administrator Level commands. 
Note:
Deleted Plug Groups cannot be automatically restored.
5.7. 
Defining Plug Parameters
The Plug Parameters Menu is used to define Plug Names, boot/sequence delay times 
and Power Up Default values for each of the Outlet Managed PDU’s Switched AC 
Outlets.  Note that this function is only available when you have accessed command 
mode using a password that permits Administrator Level commands.  The Plug 
Parameters Menu allows you to define the following parameters:  
•  Plug Name:  (Up to 16 Characters, Default = undefined.)
Note:
Plug Names must begin with either a lower case alphabetic letter 
or upper case alphabetic letter.  Plug Names cannot begin with a 
number character or symbol character.
•  Boot/Seq. Delay:  When more than one plug is switched On or a reboot cycle 
is initiated, the Boot/Sequence delay determines how much time will elapse 
before the next plug is switched On.  When the Boot/Sequence Delay is applied, 
the Outlet Managed PDU will wait for the user-defined delay period before 
switching On the next plug.  When Reboot cycles and switching actions are 
initiated, the Boot/Sequence Delay will be applied as follows:   
(Default = 0.5 Second.)
  Reboot Cycle Delay:  During a reboot cycle, the Outlet Managed PDU will 
first switch all selected plugs "Off" (with a 0.5 second pause between each 
"Off" operation), and then begin to switch selected plugs back On again, 
pausing for the user-defined Boot/Sequence Delay before switching On 
the next plug.  For example, if the Boot/Sequence Delay for Plug 3 is ten 
seconds, then the Outlet Managed PDU will pause for ten seconds before 
proceeding to the next plug.
  "On" Sequence Delay:  When two or more plugs are switched On, the 
Outlet Managed PDU will pause for the user-defined Boot/Sequence Delay 
before switching the next plug.