Справочник Пользователя для Roberts Gorden CTCU 22

Скачать
Страница из 40
SECTION 10: C
OMMISSIONING
17
10.2.2 Commissioning the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Loosen the screw cover of the outlet (burner) 
pressure test point and connect a manometer.
2. With the burner firing, measure the pressure on 
the manometer. To adjust the burner pressure, 
remove the regulator cover from the valve and 
turn the regulator adjustment screw to set the 
required burner pressure as stated in the Tech-
nical Data Tables for the correct gas and model 
on Page 6, Section 4.3.
NOTE:
 If the correct burner pressure cannot be 
reached, then check the inlet pressure to the valve, 
with the burner firing. See Technical Data Tables on 
Page 6, Section 4.3
 for inlet pressure requirement.
Do not continue to adjust the regulator if the 
pressure is not changing.
If the inlet pressure is too low to allow correct burner 
pressure setting, then the gas inlet pressure must be 
corrected before completing the commission. 
Check Gas Rate
1. After burner pressure adjustment, allow the 
heater to operate for at least 15 minutes and 
then re-check settings.
2. Remove the manometer and refit all covers to 
the valve and tighten the screw of the outlet 
pressure tap.
3. Check gas flow rate at gas meter.
10.2.3 Combustion Testing
The only adjustment to alter combustion 
performance is burner pressure. Combustion quality 
must be tested to prove correct heater operation. 
Incorrect results will indicate faults with the 
installation or appliance.
Combustion testing must be carried out with all 
covers in place. The flue gas is sampled in the flue, 
within 1 meter of the heater. The values of CO
2
 
should be between 5.7% to 8.0% for natural gas and 
6.8% to 9.2% for LPG dependant upon model.
The CO will be up to 80 ppm (0.008%) dry, air free 
dependant upon model. Temperature rise of the flue 
gases above ambient should be approximately 
130° C to 160° C. Seal test hole in flue after testing.
10.2.4 Pressure Switch
The pressure switch is factory pre-set for each 
model and is not adjustable.
10.2.5 Turning Off the Heater
Set the external controls to the "OFF" position and 
the main burner will stop.
The fan will run until it is stopped automatically by 
the fan thermostat. 
Do not use Electrical Isolator for control of 
heater. Electrical Isolator will switch off the fan. 
Heat exchanger could be damaged. Warranty will 
not cover damage to the heat exchanger if 
operated improperly.
10.2.6 External Controls
External Controls may include time switch, room 
thermostat and frost thermostat. Operate each 
control to ensure that they function correctly. Set the 
time switch (if fitted) and room thermostat to the 
users’ requirements. 
10.3 Complete the Commissioning
Ensure that all covers are fitted correctly and all test 
points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user 
including how to turn it on and off, using the controls 
fitted on site. 
Give this manual to the user.
Ensure that the user is shown and understands the 
importance of maintaining clearances to 
combustibles and the user instructions on Page 18, 
Section 11
 through Page 19, Section 11.5 and all 
warnings defined in this manual.