Справочник Пользователя для Mitsubishi Electronics QD64D2

Скачать
Страница из 154
3
 - 6
3.3 I/O Signals to the Programmable Controller CPU
3.3.1 List of I/O signals
3
SPECIFICATIONS
3.3
I/O Signals to the Programmable Controller CPU
3.3.1
List of I/O signals
The following table shows the I/O signals from the QD64D2 to the programmable 
controller CPU. 
Note that I/O numbers (X/Y) mentioned in this and the subsequent chapters are assumed 
when the QD64D2 is mounted to the null I/O slot on the main base unit.
(1) List of input signals (Signal direction: QD64D2   Programmable 
controller CPU)
 * 1 The signals are used only for the continuous comparison function.
POINT
The reserved signals above are for system use, not for users. If used (turning ON/
OFF) by a user, the functions of the QD64D2 are not guaranteed. 
Table 3.3 List of input signals
I/O
number
Signal name
I/O
number
Signal name
X00
Module READY
X10
Reserved
X01
CH1
Counter value large No.1 
X11
CH2
Counter value large No.1
X02
Counter value coincidence No.1 
X12
Counter value coincidence No.1
X03
Counter value small No.1 
X13
Counter value small No.1 
X04
Counter value large No.2  
X14
Counter value large No.2 
X05
Counter value coincidence No.2 
X15
Counter value coincidence No.2 
X06
Counter value small No.2
X16
Counter value small No.2 
X07
Reserved
X17
Reserved
X08
External preset request detection
X18
External preset request detection
X09
During continuous comparison No.1 
execution 
*1 
X19
During continuous comparison No.1 
execution 
*1
X0A
During continuous comparison No.2 
execution 
*1
X1A
During continuous comparison No.2 
execution 
*1
 
X0B
Reserved
X1B
Reserved
X0C
Reserved
X1C
Reserved
X0D
Error occurrence
X1D
Error occurrence
X0E
Warning occurrence
X1E
Warning occurrence
X0F
Reserved
X1F
Blown fuse detection flag