5
 - 2
5.1 Pulse Input and Count Methods
5.1.1 Types of the pulse input method
5
FUNCTIONS
POINT
When performing control with phase B pulse input or the subtraction count 
command (Y05) at 1-phase pulse input, always turn OFF the unused signals.
If either of phase B pulse input or the subtraction count command (Y05) is ON, 
subtraction count is performed at phase A pulse input.
2 multiples of 2 
phases
For addition count
When  B is OFF, counts on the rising edge ( ) of  A.
When  B is ON, counts on the falling edge ( ) of  A.
For subtraction 
count 
When  B is ON, counts on the rising edge ( ) of  A.
When  B is OFF, counts on the falling edge ( ) of  A.
4 multiples of 2 
phases
For addition count
When  B is OFF, counts on the rising edge ( ) of  A.
When  B is ON, counts on the falling edge ( ) of  A.
When  A is ON, counts on the rising edge ( ) of  B.
When  A is OFF, counts on the falling edge ( ) of  B.
For subtraction 
count 
When  B is ON, counts on the rising edge ( ) of  A.
When  B is OFF, counts on the falling edge ( ) of  A.
When  A is OFF, counts on the rising edge ( ) of  B.
When  A is ON, counts on the falling edge ( ) of  B.
Table 5.1 Types of the pulse input method (continued)
Pulse input 
method
Count timing
A
B
A
B
A
B
A
B