6 - 69 
MELSEC-Q
 
6   PLC PROGRAM USED FOR POSITIONING CONTROL 
 
6.5.6 Stop program 
The axis stop signal [Y4, Y5, Y6, Y7] or a stop signal from an external device is used to 
stop the control. 
Create a program to turn ON the axis stop signal [Y4, Y5, Y6, Y7] as the stop program. 
 
The process for stopping control is explained below. 
Each control is stopped in the following cases. 
 
(1)   When each control is completed normally. 
(2)   When the Servo READY signal is turned OFF. 
(3)   When a PLC CPU error occurs. 
(4)   When the PLC READY signal is turned OFF. 
(5)   When an error occurs in QD75MH. 
(6)   When control is intentionally stopped  
(Stop signal from PLC CPU turned ON, stop signal from peripheral devices) 
 
The stop process for the above cases is shown below. 
(Excluding item (1) above "When each control is completed normally".) 
 
[1] Stop 
process 
 
Stop process 
OPR control 
Manual control 
Stop cause 
Stop axis 
M code 
ON signal 
after stop 
Axis 
operation 
status 
(
Md.26
after 
stopping 
Machine 
OPR 
control 
Fast OPR 
control 
Major 
positioning 
control 
High-level 
positioning 
control 
JOG/ 
Inching 
operation 
Manual pulse 
generator 
operation 
"Forced stop input 
signal from an 
external device" 
OFF 
All axes  No change  Servo OFF 
Servo READY OFF 
 • Servo amplifier 
power supply 
OFF 
Servo 
amplifier 
disconnected 
 • Servo alarm 
During error 
Forced stop 
 • Forced stop input 
to servo amplifier 
Each 
axis 
No change 
Servo OFF 
Servo OFF or free run (The operation stops with dynamic brake) 
 
Fatal stop  
(Stop group 1) 
Hardware stroke 
limit upper/lower 
limit error 
occurrence 
Each 
axis 
No change  During error 
Deceleration stop/sudden stop  
(Select with "
Pr.37
Sudden stop group 1 sudden stop 
selection".) 
Deceleration 
stop 
Error occurs in PLC 
CPU 
No change 
PLC READY signal 
OFF 
Turns OFF 
Emergency stop  
(Stop group 2) 
Error in test mode 
All axes 
No change 
During error 
Delegation stop/sudden stop  
(Select with "
Pr.38
Sudden stop group 2 sudden stop 
selection".) 
Deceleration 
stop 
Axis error detection 
(Error other than 
stop group 1 or 2) 
Relatively safe stop  
(Stop group 3) 
"Stop" input from 
peripheral device 
Each 
axis 
No change  During error 
"Stop signal" ON 
from external 
device 
Intentional stop 
(Stop group 3) 
"Axis stop signal" 
ON from PLC CPU 
Each 
axis 
No change 
During stop 
(during 
standing 
by) 
Deceleration stop/sudden stop  
(Select with "
Pr.39
Sudden stop group 3 sudden stop 
selection".) 
Deceleration 
stop