13   COMMON FUNCTIONS 
 
13.5 External I/O signal logic switching function 
This function switches the signal logic according to the external equipment connected 
to the QD75MH or the external input signal (upper/lower limit switch, near-point dog) of 
the servo amplifier. 
For the system in which b-contact, upper limit switch, and lower limit switch are not 
used, the parameter logic setting can be controlled without wiring if it is changed to a 
"positive logic". 
When the upper limit switch, and lower limit switch are used, ensure to use them with 
b-contact. 
 
The details shown below explain about the "External I/O signal logic switching 
function". 
[1] Parameter setting details 
[2] Precautions on parameter setting 
 
[1]   Parameter setting details 
To use the "External I/O signal logic switching function", set the parameters 
shown in the following table. 
 
Buffer memory address 
Setting item 
Setting details 
Factory-
set initial 
value 
Axis 
Axis 
Axis 
Axis 
• Selection of logic of signals input from external 
device to QD75MH 
  b0  1 
Lower limit 
  b1  1 
Upper limit 
0: Negative logic, 
1: Positive logic 
  b2 
Not used 
Set "0". 
 b3 
Stop 
signal 
 b4 
External 
command/ 
switching signal 
0: Negative logic, 
1: Positive logic 
  b5 
Not used 
Set "0". 
  b6  1 
Near-point dog 
signal 
0: Negative logic, 
1: Positive logic 
  b7 
Not used 
Set "0". 
 b8 
Manual pulse 
generator input 
0: Negative logic, 
1: Positive logic 
 Pr.22 
 
Input signal logic 
selection 
  b9 to b15 
Not used 
Set "0". 
0 31 
181 
331 
481 
1: The input signal logic selection (positive/negative logic) is valid to the forced stop of the servo amplifier when 
" Pr.80   External input signal selection" is set to "1". 
2: Refer to Section 5.2 "List of parameters" for the information on detail settings. 
 
[2]   Precautions on parameter setting 
(1) The external I/O signal logic switching parameters are validated when the 
PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right after 
power-on.) 
 
(2) If each signal logic is set erroneously, the operation may not be carried out 
correctly. 
Before setting, check the specifications of the equipment to be used.