9300 Series User’s Guide
RS-485 Connections
Chapter 5 - Features and Applications 
Page 107
RS-485 Connections
Refer to the “Hardware Reference” chapter for the 9300 Series RS-485 
specifications. The communication card is designed with optical coupling that 
provides full isolation between the RS-485 communication lines and the meter 
internal circuitry. This circuitry provides protection from common mode voltages 
and incorrect connections. All inputs pass the ANSI/IEEE C37.90-1989 surge 
withstand and fast transient tests.
The communications terminal strip on the rear of the meter shows two 
communication ports: COM 1 and COM 2. (The COM 2 port is not available on the 
9300.) Up to 32 devices can be connected on a single RS-485 bus. Use a good quality 
shielded twisted pair cable for each RS-485 bus, AWG 22 (0.5 mm
2
) or larger. The 
overall length of the RS-485 cable connecting all devices cannot exceed 4000 ft. 
(1219 m). The RS-485 bus may be configured in straight-line or loop topologies.
Straight Line Topology
Loop Topology
General Bus Wiring Considerations 
Devices connected on the bus, including the meter, converter(s) and other 
instrumentation, must be wired as follows: 
The shield of each segment of the RS-485 cable must be connected to ground at 
one end only
Isolate cables as much as possible from sources of electrical noise.
Use an intermediate terminal strip to connect each device to the bus. This allows 
for easy removal of a device for servicing if necessary.