Custom Front Panel Displays
 9300 Series User’s Guide
Page 38
Chapter 2 - Using The Front Panel 
Custom Front Panel Displays
Custom front panel displays can be created showing any data the meter measures 
or calculates. Each display screen can be configured to display any measurements 
you require. You can also adjust the size of the characters in each screen so you can 
easily read the device’s display from farther away.
There are only eight display screens available for configuration. Since all eight of 
the front panel’s screen displays are factory-configured, an existing display must 
be changed if you want a custom display. Refer to “Default Front Panel Display 
Screens” on page 25 and/or “Disp
lay Configuration” on page 50 for details on the 
eight default display screens.
The technical note Custom Front Panel Displays has complete details for 
personalizing your meter’s display screens.
Before Customizing the Front Panel
In order for the customized screens to be displayed in the front panel’s display, the 
meter’s Display Mode must be properly set. Ensure that the Display Options 
module’s Display Mode setup register is set to P
ROGRAMMABLE
. This is the default 
setting. If it is required, you can use the meter’s front panel or ACCESS software to 
set this register.
Customizing Displays Using the Front Panel
The S
CREEN
 S
ETUP
 menu screen allows you to change the data displayed on the 
eight display screens using the front panel (see “Screen Setup Menu” on page 34).
Customizing Displays Using Designer
The front panel display of the 9300 Series is controlled by the Display modules and 
Display Options modules. Refer to the ION Programmer’s Reference for detailed 
descriptions of the Display module and the Display Options module. Refer to 
“ION Enterprise: Designer” on page 83 for details on using Designer.
Display Module
A Display module controls which values are displayed on a display screen, and 
how these values are presented. Up to four parameters can be linked to a Display 
module — these parameters appear on the display screen when the module is 
activated.