9300 Series User’s Guide
Using the Modbus RTU Protocol
Chapter 3 - Default Meter Functionality 
Page 57
Modbus Slave Module #2 Links
Modbus Slave Module #3 Links
Average L-L Voltage
Vll avg
Power Meter
Modbus Slave #1 – Source Input #8
40018
Phase A Current
I a
Power Meter
Modbus Slave #1 – Source Input #9
40019
Phase B Current
I b
Power Meter
Modbus Slave #1 – Source Input #10
40020
Phase C Current
I c
Power Meter
Modbus Slave #1 – Source Input #11
40021
Average Current
I avg
Power Meter
Modbus Slave #1 – Source Input #12
40022
Voltage Unbalance
V unbal
Power Meter
Modbus Slave #1 – Source Input #13
40023
Current Unbalance
I unbal
Power Meter
Modbus Slave #1 – Source Input #14
40024
Line Frequency
Freq
Power Meter
Modbus Slave #1 – Source Input #15
40025
L-N Voltage Phase A
Vln a
Power Meter
Modbus Slave #1 – Source Input #1
40011
Measurement 
Label
Source ION Module
Modbus Module and Input Number
Modbus Register
Measurement 
Label
Source ION Module
Modbus Module and Input Number
Modbus Register
Phase A kW
kW a
Power Meter
Modbus Slave #2 – Source Input #1
40027-40028
Phase B kW
kW b
Power Meter
Modbus Slave #2 – Source Input #2
40029-40030
Phase C kW
kW c
Power Meter
Modbus Slave #2 – Source Input #3
40031-40032
Total kW
kW tot
Power Meter
Modbus Slave #2 – Source Input #4
40033-40034
Phase A kVAR
kVAR a
Power Meter
Modbus Slave #2 – Source Input #5
40035-40036
Phase B kVAR
kVAR b
Power Meter
Modbus Slave #2 – Source Input #6
40037-40038
Phase C kVAR
kVAR c
Power Meter
Modbus Slave #2 – Source Input #7
40039-40040
Total kVAR
kVAR tot
Power Meter
Modbus Slave #2 – Source Input #8
40041-40042
Phase A kVA
kVA a
Power Meter
Modbus Slave #2 – Source Input #9
40043-40044
Phase B kVA
kVA b
Power Meter
Modbus Slave #2 – Source Input #10
40045-40046
Phase V kVA
kVA c
Power Meter
Modbus Slave #2 – Source Input #11
40047-40048
Total kVA
kVA tot
Power Meter
Modbus Slave #2 – Source Input #12
40049-40050
Phase A signed PF
PF sign a
Power Meter
Modbus Slave #2 – Source Input #13
40051-40052
Phase B signed PF
PF sign b
Power Meter
Modbus Slave #2 – Source Input #14
40053-40054
Phase C signed PF
PF sign c
Power Meter
Modbus Slave #2 – Source Input #15
40055-40056
Measurement 
Label
Source ION Module
Modbus Module and Input Number
Modbus Register
kW Thermal Dmd
kW td
Thermal Demand
Modbus Slave #3 – Source Input #1
40059-40060
kVAR Thermal Dmd
kVAR td
Thermal Demand
Modbus Slave #3 – Source Input #2
40061-40062
kVA Thermal Dmd 
kVA td
Thermal Demand
Modbus Slave #3 – Source Input #3
40063-40064
Max kW Th Dmd
kW td mx
Maximum
Modbus Slave #3 – Source Input #4
40065-40066