E6581315
40
7. Communication parameters
The settings of communication-related parameters can be changed from the operation panel and
the external controller (computer). Note that there are two types of parameters: parameters whose
settings take effect immediately after the setting and parameters whose settings do not take effect
until the inverter is turned back on or reset.
the external controller (computer). Note that there are two types of parameters: parameters whose
settings take effect immediately after the setting and parameters whose settings do not take effect
until the inverter is turned back on or reset.
Com-
munica-
tion
Number.
Title
Function
Adjustment range
Unit
Default
setting
Valid
Reference
0800
Baud rate
(2-wire RS485)
(2-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
1: 19200bps
2: 38400bps
-
1
After reset.
Section 7.1
0801
Parity (common)
0: Non parity
1: Even parity
2: Odd parity
1: Even parity
2: Odd parity
-
1
After reset.
Section 7.1
0802
Inverter number
(common)
(common)
0-247
1
0
Real time
Section 7.2
0803
Communication
time-out time
(common)
time-out time
(common)
0:OFF
1-100s
1-100s
1s
0
Real time
Section 7.3
2-wire
4-wire
0
-
-
1
t alarm
-
2
Err5 trip
-
3
-
t alarm
4
t alarm
t alarm
5
Err5 trip
t alarm
6
-
Err5 trip
7
t alarm
Err5 trip
0804
Communication
time-out action
(common)
time-out action
(common)
8
Err5 trip
Err5 trip
1
8
Real time
Section 7.3
0805
Send waiting time
(2-wire RS485)
(2-wire RS485)
0.00: Default
0.01-2.00s
0.01-2.00s
0.01s
0.00
Real time
Section 7.4
0806
Inverter-to-inverter
communication
communication
(2-
wire RS485)
0:Slave (issues a 0Hz command if some-
thing goes wrong with the master)
1:Slave (continues operation if something
goes wrong with the master)
2:Slave (trips for emergency stop if
something goes wrong with the master)
3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque com-
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque com-
mand)
-
0
After reset.
Chapter 6
0807
Protocol selection
(2-wire RS485)
(2-wire RS485)
0: TOSHIBA
1:MODBUS-RTU
1:MODBUS-RTU
-
0
After reset.
Chapter 3
0810
Frequency point
selection
selection
0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option
1:2-wire RS485
2:4-wire RS485
3:Communication add option
-
0
Real time
Section 6.1
0811
Point 1 setting
0-100%
-
0
Real time
0812
Point 1 frequency
0-Hz
0.01Hz
0.0
Real time
0813
Point 2 setting
0-100%
-
100
Real time
0814
Point 2 frequency
0-Hz
0.01Hz
60.0
Real time
Section 6.1
0820
Communication
speed
(4-wire RS485)
speed
(4-wire RS485)
0: 9600bps
1: 19200bps
2: 38400bps
1: 19200bps
2: 38400bps
-
1
After reset.
Section 7.1
0825
Send waiting time
(4-wire RS485)
(4-wire RS485)
0.00: Normal
0.01-2.00s
0.01-2.00s
0.01s
0.00
Real time
Section 7.4