8.3. Utilizing panel (LEDs and keys) by communication
The VF-AS1 can display data that is not related to the inverters through an external controller or
other means.    Input by key operations can also be executed.    The use of inverter resources re-
duces the cost for the entire system.
8.3.1.   LED setting by communication
Desired
 LED information can be displayed by communication.
<How to Set>
Set the standard monitor display selection parameter to “communication LED setting
(=).”
When in the standard monitor mode status, LED information is displayed according to the setting of
Communication Number FA65.    (Set to Communication Number FA65 = 1 and initial data “”
in
 
shipment setting)
In case of an alarm while setting communication LEDs, the alarm display will alternately display
specified LED data and alarm message.
For example, if an over-current alarm (alarm display “”) occurs while “.” is displayed by this
function, “” and “.” will be displayed alternately.
Commu-
nication
Number.
Parameter Name
Range
Shipment
setting
FA65
Select display by communication
0: Numeric data    (FA66, FA67, FA68)
1: ASCII data 1 (FA70, FA71, FA72, FA73,
FA74)
2: ASCII data 2 (FA75, FA76, FA77, FA78,
FA79)
1
FA66
Numeric display data
(Enabled if FA65=0)
0-9999
0
FA67
Decimal point position
(Enabled if FA65=0)
0: No decimal point (xxxx)
1: First digit below decimal point (xxx.x)
2: Second digit below decimal point (xx.xx)
0
FA68
LED data 0 for unit
(Enabled if FA65=0)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0
FA70
ASCII display data 1, first digit from
left
(Enabled if FA65=1)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
64H (’d’)
FA71
ASCII display data 1, second digit
from left
(Enabled if FA65=1)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
41H (’A’)
FA72
ASCII display data 1, third digit from
left
(Enabled if FA65=1)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
74H (’t’)
FA73
ASCII display data 1, fourth digit from
left
(Enabled if FA65=1)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
41H (’A’)
FA74
LED data 1 for unit
(Enabled if FA65=1)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0
FA75
ASCII display data 2, first digit from
left
(Enabled if FA65=2)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
30H (’0’)
FA76
ASCII display data 2, second digit
from left
(Enabled if FA65=2)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
30H (’0’)
FA77
ASCII display data 2, third digit from
left
(Enabled if FA65=2)
0 – 256 (0 – FFH)
(See ASCII LED display code chart))
30H (’0’)
FA78
ASCII display data 2, fourth digit from
left
(Enabled if FA65=2)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
30H (’0’)
FA79
LED data 2 for unit
(Enabled if FA65=2)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on