Control circuit
37
2
2.6.2
Details on the control circuit terminals of the 
converter unit (FR-CC2)
The input signal function of the terminals in 
 can be selected by setting Pr.178, Pr.187, Pr.189 to Pr.195 (I/O terminal 
function selection).
For the parameter details, refer to the FR-CC2 Instruction Manual.
Input signal
Ty
p
e Terminal
Symbol
Terminal name
Terminal function description
Rate Specification
Cont
act
 input
RES
Reset
Use this signal to reset a fault output provided when a protective function 
is activated. Turn ON the RES signal for 0.1 s or longer, then turn it OFF.
In the initial setting, reset is always enabled. By setting Pr.75, reset can 
be set enabled only at fault occurrence of the converter unit. The inverter 
recovers about 1s after the reset is released.
Input resistance 
4.7 k
Voltage when 
contacts are open: 21 
to 27 VDC
When contacts are 
short-circuited: 4 to 6 
mADC
OH
External thermal 
relay input
The external thermal relay input (OH) signal is used when using an 
external thermal relay or a thermal protector built into the motor to 
protect the motor from overheating.
When the thermal relay is activated, the inverter trips by the external 
thermal relay operation (E.OHT).
RDI
Contact input
The function can be assigned by setting Pr.178.
SD
Contact input 
common (sink)
Common terminal for contact input terminal (sink logic) and terminal FM 
———
External transistor 
common (source)
Connect this terminal to the power supply common terminal of a 
transistor output (open collector output) device, such as a programmable 
controller, in the source logic to avoid malfunction by undesirable 
current.
24 VDC power supply 
common
Common terminal for the 24 VDC power supply (terminal PC, terminal 
+24)
Isolated from terminals 5 and SE.
PC
External transistor 
common (sink)
Connect this terminal to the power supply common terminal of a 
transistor output (open collector output) device, such as a programmable 
controller, in the source logic to avoid malfunction by undesirable 
current.
Power supply voltage 
range 19.2 to 28.8 
VDC
Permissible load 
current 100 mA
Contact input 
common (source)
Common terminal for contact input terminal (source logic).
24 VDC power supply 
common
Can be used as a 24 VDC 0.1 A power supply.
Power
 s
uppl
y input
+24
24 V external power 
supply input
For connecting a 24 V external power supply.
If a 24 V external power supply is connected, power is supplied to the 
control circuit while the main power circuit is OFF.
Input voltage 23 to 
25.5 VDC
Input current 1.4 A or 
less