Power supply harmonics
67
3
3.2
Power supply harmonics
3.2.1
Power supply harmonics
The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power factor 
correction capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and 
transmission path. Take the following countermeasure suppression techniques.
 • The differences between harmonics and noises
 • Countermeasures
NOTE
 • The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged by 
the harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate overcurrent 
protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is driven by the 
inverter. For power factor improvement, install a reactor on the inverter input side or in the DC circuit.
Item
Harmonics
Noise
Frequency
Normally 40th to 50th degrees or less (3 kHz 
or less).
High frequency (several 10 kHz to 1 GHz order).
Environment
To-electric channel, power impedance.
To-space, distance, wiring path,
Quantitative understanding
Theoretical calculation possible.
Random occurrence, quantitative grasping difficult.
Generated amount
Nearly proportional to the load capacity.
Changes with the current variation ratio. (Gets larger as 
switching speed increases.)
Affected equipment immunity
Specified by standards per equipment.
Different depending on maker's equipment specifications.
Countermeasure
Provide a reactor.
Increase distance.
The harmonic current generated from the inverter 
to the input side differs according to various 
conditions such as the wiring impedance, whether 
a reactor is used or not, and output frequency and 
output current on the load side.
For the output frequency and output current, we 
understand that this should be calculated in the 
conditions under the rated load at the maximum 
operating frequency.

The converter unit (FR-CC2) is equipped with the DC reactor.
DC reactor 
∗1
Inverter/
converter
R
S
T
Z
Y
X
U
V
W
R/L1
S/L2
T/L3
M
AC reactor
(FR-HAL)
Do not insert power 
factor improving capacitor.
MCCB
MC
Power supply