Countermeasures against deterioration of the 400 V class motor insulation
72
NOTE
 • Before wiring or inspection for a PM motor, confirm that the PM motor is stopped. In an application, such as fan and blower, 
where the motor is driven by the load, a low-voltage manual contactor must be connected at the inverter's output side, and 
wiring and inspection must be performed while the contactor is open. Otherwise you may get an electric shock.
 • Do not open or close the contactor while the inverter is running (outputting).
3.5
Countermeasures against deterioration of 
the 400 V class motor insulation
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially in a 
400 V class motor, the surge voltage may deteriorate the insulation. When the 400 V class motor is driven by the inverter, 
consider the following countermeasures:
 • Countermeasures
(With induction motor)
It is recommended to take one of the following countermeasures:
 • Rectifying the motor insulation and limiting the PWM carrier frequency according to the wiring length
For the 400 V class motor, use an insulation-enhanced motor.
Specifically,
- Order a "400 V class inverter-driven insulation-enhanced motor".
- For the dedicated motor such as the constant-torque motor and low-vibration motor, use an "inverter-driven dedicated 
motor".
- Set Pr.72 PWM frequency selection as indicated below according to the wiring length.
 • Suppressing the surge voltage on the inverter side
- If the motor capacity is 280 kW or lower, connect the sine wave filter (MT-BSL/BSC) to the output side.
(With PM motor)
 • When the wiring length exceeds 50 m, set "9" (6 kHz) or less in Pr.72 PWM frequency selection
NOTE
 • When using the optional sine wave filter (MT-BSL/BSC), set Pr.72="25" (2.5 kHz).
 • For the details of the sine wave filter (MT-BSL/BSC), refer to the Instruction Manual of each option.
 • A sine wave filter (MT-BSL/BSC) can be used under V/F control. Do not use the filters under different control methods.
 • The carrier frequency is limited during PM sensorless vector control. (Refer to the FR-A800 Instruction Manual (Detailed))
Wiring length
100 m or shorter
Longer than 100 m
Pr.72 PWM frequency selection
6 (6 kHz) or lower
4 (4 kHz) or lower