5-42
DELTA(P)
5.3.10  
Pulse conversions of direct outputs (DELTA(P))
DELTA(P)
Function
(1) Conducts pulse output of direct access output (DY) designated by 
.
If DELTA DY0 has been designated, the resulting operation will be identical to the ladder 
shown below, which uses the SET/RST instructions.
[Ladder using the DELTA instruction]
[Ladder using the SET/RST instructions]
[Operation]
(2) The DELTA (P) instruction is used by commands for leading edge execution for an intelligent 
function module.
Operation Error
(1) In the following case, an operation error occurs, the error flag (SM0) turns ON, and an error 
code is stored into SD0.
 • A direct access output number designated by 
 has exceeded the CPU module output 
range.
(Error code: 4101)
: Bit for which pulse conversion is to be conducted (bits)
Setting 
Data
Internal Devices 
R, ZR
J
\
U
\G
Zn
Constants
Other
DY
Bit
Word
Bit
Word
––
Basic
Process
High
performance
Redundant Universal
Command
Command
DELTA
DELTAP
D
DELTA
D
DELTAP
D
D
D
X100
DY0
DELTA
X100
DY0
SET
DY0
RST
X100
ON
OFF
DY0
ON
OFF
ON
END processing
DELTA DY0
DELTA DY0
D