Canceling of Errors
Q series CPU module can perform the cancel operation for errors only when the errors allow 
the CPU module to continue its operation.
To cancel the errors, follow the steps shown below.
1) Eliminate the cause of the error.
2) Store the error code to be canceled in the special register SD50.
3) Energize the special relay SM50 (OFF   ON).
4) The error to be canceled is canceled.
  
After the CPU module is reset by the canceling of the error, the special relays, special 
registers, and LEDs associated with the error are returned to the status under which the 
error occurred.
If the same error occurs again after the cancellation of the error, it will be registered again in 
the error history.
When multiple enunciators(F) detected are canceled, the first one with No. F only is 
canceled.
Refer to the following manual for details of error canceling.
QCPU User's Manual (Function Explanation, Program Fundamentals)
(1) When the error is canceled with the error code to be canceled stored in the 
SD50, the lower one digit of the code is neglected.
(Example)
If error codes 2100 and 2101 occur, and error code 2100 to cancel error code 
2101.
If error codes 2100 and 2111 occur, error code 2111 is not canceled even if 
error code 2100 is canceled.
(2) Errors developed due to trouble in other than the CPU module are not 
canceled even if the special relay (SM50) and special register (SD50) are 
used to cancel the error.
(Example)
Since "SP. UNIT DOWN" is the error that occurred in the base unit (including 
the extension cable), intelligent function module, etc. the error cause cannot 
be removed even if the error is canceled by the special relay (SM50) and 
special register (SD50).
Refer to the error code list and remove the error cause.