Job Name: 
Location:
Drawing Reference: 
Schedule No.
System No.: 
Date:
Outdoor Unit:
 16-TON PURY-P192TSHMU-A-BS
(Consists of Two PURY-P96THMU-A-BS and One CMY-R100VBK Twinning Kit)
OutdOOr VrFZ HEAt rEcOVEry SyStEM FEAturES
• 3-phase, 208/230V systems
• Modular variable refrigerant flow zoning (VRFZ) systems; 
  smaller capacity units can be piped together to form a single, 
  large-capacity two-pipe system
• Compact size for each outdoor module; can be transported 
  through standard-sized doorways for installation
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static  
  pressure; factory set to 0"WG
• Max. Total Refrigerant Piping Length: 1,804' (P72,96); 1,969' 
  (P120,144,168); 2,461' (P192); 2,625' (P216,240); Max.  
  Line Length: 541'; Max. Control Wiring Length: 1,650'
• Connects to CITY MULTI indoor units; controlled via  
  CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets with 
  thermoset polyester-resin
• Operating Temperature Range 
  Cooling (Outdoor): 23° ~ 109°F (-5° ~ +43°C) DB
  Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PURY-P96THMU-A-BS
PURY-P96THMU-A-BS
OPtIONAL PArtS
□ Twinning Kit*.…………………………………...……...CMY-R100VBK
□ Branch Joint (T-Branch: ≤ 72,000 Btu/h).………….CMY-Y102S-G2
□ Branch Joint (T-Branch: 73,000-144,000 Btu/h).……….CMY-Y102L-G2
□ Joint Adapter (Port Connector>54,000 Btu/h).………….CMY-R160J
□ Main BC Controller.…………………..CMB-P108/1010/1013/1016NU-GA
□  Sub  BC  Controller.…………………CMB-P104/108NU-GB/-1016NU-HB
* Twinning Kit is necessary to combine the refrigerant flows of the  
   modules and is included in the outdoor unit set. 
Specifications
System 
Module 1 
Module 2
Unit Type
PURY-P192TSHMU-A-BS
PURY-P96THMU-A-BS
PURY-P96THMU-A-BS
Nominal Cooling Capacity
Btu/h
192,000
96,000
96,000
Nominal Heating Capacity
Btu/h
200,000
108,000
108,000
External Dimensions (H x W x D) In. / mm
Refer to Module Data
65 x 48-1/16 x 29-15/16 /  
1,650 x 1,220 x 760
65 x 48-1/16 x 29-15/16 / 
1,650 x 1,220 x 760
Net Weight
Lbs. / kg
1,170 / 530
585 / 265
585 / 265
Electrical Power Requirements
Voltage, Phase, Hertz
Refer to Module Data**
208-230V, 3-phase, 60Hz
Cooling Power Input
kW
17.04
Refer to System Data
Heating Power Input
kW
15.85
Cooling Current (208/230V)
A
52.5 / 47.5
Refer to System Data
Heating Current (208/230V)
A
48.8 / 44.2
Minimum Circuit Ampacity 
(MCA)**
A
Refer to Module Data**
35 / 32**
35 / 32**
Maximum Overcurrent  
Protection (MOCP)**
A
Refer to Module Data**
40 / 40**
40 / 40**
Piping Diameter
Refer to System Data
From Twinning Kit to Indoor Units 
(Brazed) (In. / mm)
Liquid (High Pressure)
7/8 / 22.2
Gas (Low Pressure)
1-1/8 / 28.58
From Modules to Twinning Kit 
(Brazed) (In. / mm)
Liquid (High Pressure)
Refer to Module Data
3/4 / 19.05
3/4 / 19.05
Gas (Low Pressure)
7/8 / 22.2
7/8 / 22.2
Indoor Unit
Total Capacity
50 to 150% of ODUs
Refer to System Data
Model / Quantity
P06 ~ P96 / 1 to 48
Sound Pressure Levels
dB(A)
62.0
58.0
58.0
Fan
Refer to Module Data
Type x Quantity
Propeller Fan x 1
Propeller Fan x 1
Airflow Rate
cFM
7,750
7,750
Direct-drive Inverter Motor Output
kW
0.92
0.92
Compressor Operating Range
9% to 100%
Refer to System Data
Compressor Type x Quantity
Refer to Module Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Compressor Motor Output
kW
7.0
7.0
Compressor Crankcase Heater
kW
0.057
0.057
Refrigerant
Refer to Module Data
R410A
Lubricant
MEL32
High-pressure Protection Device
Refer to Module Data
601 psi / 4.15 MPa
601 psi / 4.15 MPa
Compressor / Fan Protection Device
Overheat Protection / Thermal Switch Overheat Protection / Thermal Switch
Inverter Protection Device
Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;  
≥1μm to 1.5μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.